2006-10-25 11:32:17**** UNSAT *****
  
 *** PLEASE KNOW, ONCE AN ADDRESS IS GRANTED AND GIVEN,
 THIS NEW ADDRESS SHALL BE STATED IN THE TITLE BLOCKS OF
 SAID PLANS.
 FAC 61G1-16.004
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS. 2002 NFPA-70(NEC), 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT ALL AIC RATINGS FOR NEW SERVICE
 EQUIPMENT. 110.9, 240.12
  
 3) NOTE; PLEASE SEE NFPA-72 DEFINITIONS AS IT HAS BEEN
 COMMON ACCEPTANCE THAT THE SMOKE ALARMS ARE SHOWN
 TYPICALLY AS SD'S WHICH IS ACTUALLY CONSIDERED SMOKE
 DEETCTORS WHICH ONLY DETECT SMOKE AND ARE PART OF A
 FIRE ALARM SYSTEM. PLEASE KNOW AS THE IS A SFR AND IT
 DOES NOT REQUIRE A FA SYSTEM,. PLEASE INDICATE THESE AS
 "SA"'S SMOKE ALARMS AS THESE ARE DEVICES THAT DETECT
 AND PROVIDE AN AUDIBLE SIGNAL AS REQUIRED. PLEASE SEE
 THIS HAS BEEN CONFIRMED WITH AN INTERPRETATION FROM
 NFPA- ON A RECENT CODE PANEL MEETING.
  
 4) NOTE: PLEASE SEE MISSING EGRESS LITHING CONTROL AND
 LT FIXTURE OF SOME SORT AT REAR OF DWELLING. 210.70,
 AND NFPA-101 7.8.
  
 5) NOTE: PLEASE INDICATE THE REQUIRED DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3. DOES NOT INDICATE
 BATH ON PANEL SCHEDULE. PLEASE KNOW THAT THE PANEL
 SCHEDULE SHALL BE SPECIFIC IN ORDER TO REVIEW FOR CODE
 COMPLIANCE.,
 408.4.310.16,240.4 TEC.
  
 6) NOTE: PLEASE SHOW LOAD CALCULATIONS PER NEC 220.31,
 METHOD CHOSEN IS UP TO DESIGNER, HOWEVER PLEASE SEE MIN
 VA/WATTS PER SQ FT ETC SHALL BE SHOWN.
  
 ** A A NOTE TO DESIGN PROFESSIONALS , PLEASE SEE FS
 481.229(1) FS 471.025
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]