| Date |
Text |
| 2006-10-25 11:32:17 | **** UNSAT ***** |
| | |
| | *** PLEASE KNOW, ONCE AN ADDRESS IS GRANTED AND GIVEN, |
| | THIS NEW ADDRESS SHALL BE STATED IN THE TITLE BLOCKS OF |
| | SAID PLANS. |
| | FAC 61G1-16.004 |
| | |
| | 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| | PLANS. 2002 NFPA-70(NEC), 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SUBMIT ALL AIC RATINGS FOR NEW SERVICE |
| | EQUIPMENT. 110.9, 240.12 |
| | |
| | 3) NOTE; PLEASE SEE NFPA-72 DEFINITIONS AS IT HAS BEEN |
| | COMMON ACCEPTANCE THAT THE SMOKE ALARMS ARE SHOWN |
| | TYPICALLY AS SD'S WHICH IS ACTUALLY CONSIDERED SMOKE |
| | DEETCTORS WHICH ONLY DETECT SMOKE AND ARE PART OF A |
| | FIRE ALARM SYSTEM. PLEASE KNOW AS THE IS A SFR AND IT |
| | DOES NOT REQUIRE A FA SYSTEM,. PLEASE INDICATE THESE AS |
| | "SA"'S SMOKE ALARMS AS THESE ARE DEVICES THAT DETECT |
| | AND PROVIDE AN AUDIBLE SIGNAL AS REQUIRED. PLEASE SEE |
| | THIS HAS BEEN CONFIRMED WITH AN INTERPRETATION FROM |
| | NFPA- ON A RECENT CODE PANEL MEETING. |
| | |
| | 4) NOTE: PLEASE SEE MISSING EGRESS LITHING CONTROL AND |
| | LT FIXTURE OF SOME SORT AT REAR OF DWELLING. 210.70, |
| | AND NFPA-101 7.8. |
| | |
| | 5) NOTE: PLEASE INDICATE THE REQUIRED DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210.52D, 210.11C3. DOES NOT INDICATE |
| | BATH ON PANEL SCHEDULE. PLEASE KNOW THAT THE PANEL |
| | SCHEDULE SHALL BE SPECIFIC IN ORDER TO REVIEW FOR CODE |
| | COMPLIANCE., |
| | 408.4.310.16,240.4 TEC. |
| | |
| | 6) NOTE: PLEASE SHOW LOAD CALCULATIONS PER NEC 220.31, |
| | METHOD CHOSEN IS UP TO DESIGNER, HOWEVER PLEASE SEE MIN |
| | VA/WATTS PER SQ FT ETC SHALL BE SHOWN. |
| | |
| | ** A A NOTE TO DESIGN PROFESSIONALS , PLEASE SEE FS |
| | 481.229(1) FS 471.025 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |