2006-12-07 16:03:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. SHT P-1 THE SANT. AND WATER PIPING TO THE DRINKING
 FOUNTAIN REQUIRED BY TABLE 403.1 IS NOT INDICATED ON
 THE FLOOR PLAN, NOR ON THE RISERS.
 PLEASE SHOW PIPING FOR THE DRINKING FOUNTAIN.
  
 2.SHT P-1 ONLY THE FIXTURES FROM THE BATHROOM GROUP
 SHALL CONNECT TO THE WET VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES, (SINK FROM ROOM 104),
 SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION
 909.1
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN. SHOW
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS IF
 A HI/LOW FIXTURE. IF NOT A HI/LOW FIXTURE, PLEASE SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  