| Date |
Text |
| 2006-10-28 17:41:38 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE ADJUST PLANS AND PERMIT APPLICATION |
| | ONCE A SUITE/UNIT NUMBER IS GIVEN. A SEARCH OF ALL THE |
| | EXTENSIONS FOR THIS ADDRESS/ PCN DO NOT SHOWANY |
| | ALPHABETIC LETTERING WITH NUMERICAL IDENTIFICATION |
| | FOLLOWING. IE "B-6". THIS WILL BE GIVEN BY ADDRESSING |
| | REVIEWER AND PLEASE ADJUST AS NEEDED ON THE TITLE |
| | BLOCKS FOR PLANS. |
| | |
| | 2)NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT. PER |
| | 600.5, 220.3B6 |
| | |
| | 3) NOTE: PLEASE VERIFY THE USE OFWIRING PER 517.13 |
| | (A)(B). |
| | |
| | 4) NOTE: PLEASE SEE RISER MENTIONS THE MAIN AND FEEDERS |
| | AS "ASSUMED", PLEASE KNOW, THIS SHALL BE VERIFIED AT |
| | THIS TIME AND STATED ACCORDINGLY. |
| | 240.4,310.16, ETC |
| | |
| | 5) NOTE: PLEASE INDICATE NEW OR EXISTING RTU GFI |
| | RECEPT. |
| | 210.63 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |