| Plan Review Notes For Permit 06100840 |
| Permit Number |
06100840 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-01 14:31:30 | DENIED | | | | | | 1.DOORS #2 AND 3 SHALL HAVE A MINIMUM 24" CLEARANCE | | | AT THE LATCH SIDE OF THE DOOR. SEE | | | FBC 11.67 PUSH SIDE CLEARANCE. | | | | | | 2.INFORMATION COUNTERS SHALL COMPLY WITH FBC 11-7.2 | | | (1) FOR HEIGHT AND WIDTH.SHOW DETAIL ON PLANS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE | | | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561-805-6672 | | | | | | |
|