| 2006-12-10 09:25:05 | ***** UNSAT ********* |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC, |
| | HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT |
| | PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY |
| | ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER |
| | "(OTHER PERMIT NUMBER)". |
| | |
| | 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT |
| | SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION? |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF |
| | MOTOR FOR MAX LOCKED ROTOR CURRENT ETC. |
| | THIS IS ALSO REQUIRED FOR EACH RECORD SET OF PLANS. |
| | 110.3, 90.7, ETC |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE A 4X FEE WAS ISSUED AT JOBSITE AND |
| | HOLD WAS IN SYSTEM, THE ADDITIONAL FEE FOR WORK DONE |
| | WITHOUT PERMITS IS $333.00 WHICH IS REQUIRED AT THIS |
| | TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |