| 2006-11-02 07:21:11 | ***** UNSAT ********* |
| | |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR |
| | INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE |
| | BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR |
| | WHO APPLIES. |
| | |
| | 2) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC, |
| | HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT |
| | PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY |
| | ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER |
| | "(OTHER PERMIT NUMBER)". |
| | |
| | 3) NOTE: PLEASE CLARIFY THE OCP ON THE FPC AS SHOWN. |
| | SHOWS 1000A, HOWEVER THIS IS BE TAKEN THAT THIS IS THE |
| | LRC?? PLEASE INDICATE THE NORMAL/ STANDARD OCP RATING. |
| | PLEASE VERIFY THIS AS THE SEC'S SHOWN ARE ONLY SIZED AT |
| | 2/0'S WHICH ARE RATED FOR 175A'S ONLY PER 310.16, |
| | 110.14. |
| | PLEASE VERIFY AND SHOW. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT |
| | SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION.? |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF |
| | MOTOR FOR MAX LOCKED ROTOR CURRENT ETC. |
| | 110.3, 90.7, ETC |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN |
| | APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS |
| | THE VALUE SEEMS LOW. |
| | FBC 108.3. |
| | |
| | 6) NOTE: PLEASE MAKE NOTE OF THE CONDUITS ENTERING THE |
| | FPC SHALL BE ENCASED IN CONCRETE. |
| | NFPA-20, NFPA-70 |
| | PLEASE BE SURE THE ABOVE CODES ARE STATED ON PLANS AT A |
| | MIN. |
| | PLEASE SEE 695 OF THE NEC AND CHAPTERS 6 AND 7 FOR |
| | INSTALLATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |