| 2006-11-30 19:28:49 | ****** UNSAT2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | |
| | 1) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR |
| | INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE |
| | BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR |
| | WHO APPLIES. |
| | |
| | 2) NOTE: NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE |
| | NEW METER CENTERS. |
| | 110.3,90.7 |
| | PLEASE SEE OTHER COMMENTS BELOW FOR METER CENTERS. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 6) NOTE:NO, NOT CLEAR WHAT THIS IS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO FPL? |
| | PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING; |
| | HOWEVER THIS IS IN QUESTION AT THIS TIME. |
| | 110.3, 90.7. |
| | IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK |
| | EXISTING? |
| | |
| | 7) NOTE: NO, STILL SHOWN. AS THIS IS BEING INDICATED |
| | THE MAIN 1 OF 6, PLEASE INDICATE MAIN, HOWEVER NOT IN |
| | SCOPE ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE REMOVED FIRE PUMP AND ASSOCIATED EQUIPMENT FROM |
| | RISER WHICH IS NOT IN THIS SCOPE OF WORK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS. PLEASE SEE |
| | SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY CLOSE, |
| | PLEASE VERIFY. |
| | PLEASE SEE TABLES IN CHAPTER 9. |
| | |
| | 10) NOTE:VOLTAGE DROP PROVIDED, HOWEVER FBC |
| | 13-413.1.ABC.1.1. PLEASE SEE FEEDER WHICH INDICATES 4 % |
| | ETC AND OTHERS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO THE METER |
| | CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S ETC ARE |
| | OVER 200FT. |
| | |
| | 11) NOTE:OK, HOWEVER SEE NOTE ABOVE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE ALSO PROVIDE A WORST CASE VD ON APT/CONDO |
| | FEEDER(S). |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: OK |
| | |
| | 15) NOTE:NO? UNCLEAR AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE VALUE ON SCOPE OF WORK WHEN APPLICATION IS |
| | MADE MAY BE ADJUSTED. PLEASE VERIFY AS THE VALUE SEEMS |
| | LOW. PLEASE KNOW VALUE PANEL FOR EACH UNIT CANE BE |
| | SUBTRACTED AS THESE WILL BE SEPARATE, HOWEVER ALL NEW |
| | FEEDERS FOR UNITS, FEEDERS FOR METER CENTERS AND NEW |
| | METER CENTERS SHALL BE INCLUDED. VALUE SHALL INCLUDE |
| | ALL LABOR AND MATERIALS EVEN IF ANY EQUIPMENT IS OWNER |
| | SUPPLIED. |
| | FBC 108.3. |
| | |
| | 16) NOTE: OK. |
| | |
| | *** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FIRE PUMP MAIN/CONTROLLER |
| | INFORMATION AS SHOWN ON THIS RISER DOES NOT CORRELATE |
| | WITH THE PUMP CONTROLLER WHICH HAS YET TO BE APPLIED |
| | FOR. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |