| 2006-11-02 08:20:40 | ***** UNSAT ********* |
| | |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR |
| | INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE |
| | BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR |
| | WHO APPLIES. |
| | |
| | 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | FOR THE NEW METER CENTERS. |
| | 110.3,90.7 |
| | PLEASE SEE OTHER COMMENTSBELOW FOR METER CENTERS. |
| | |
| | 3) NOTE: PLEASE CORRELATE METER CENTER DESIGNATIONS. |
| | PLEASE SEE METER BANK BOX #4 IS FOR METER CENTER #3, |
| | AND MC #3 SHOWS # 4 BOX. |
| | THIS WAS REDLINED ON PLANS. |
| | |
| | 4) NOTE: PLEASE PROVIDE ACTUAL MC DESIGNATION AND |
| | LABELING IN THE MAIN SWITCH GEAR EQUIPMENT. PLEASE ALSO |
| | CLARIFY THE OCP AS SHOWN. SOME ARE SHOWN DIFFERENTLY AS |
| | 500A, RATED WITH 600A FUSES, AND OTHERS 600A RATED WITH |
| | THE 450A OCP. PLEASE CORRELATE AND COORDINATE THESE. |
| | |
| | 5) NOTE: PLEASE CLARIFY WHERE MAIN 1 IS? 2OF 6 THROUGH |
| | 6OF 6 IS SHOWN , HOWEVER COULD NOT LOCATED 1? |
| | 230.70,230.72 |
| | |
| | 6) NOTE: PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO |
| | FPL? PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING |
| | , HOWEVER THIS IS IN QUESTION AT THIS TIME. |
| | 110.3, 90.7. |
| | IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK |
| | EXISTING? |
| | |
| | 7) NOTE: PLEASE REMOVED FIRE PUMP AND ASSOCIATED |
| | EQUIPMENT FROM RISER WHICH IS NOT IN THIS SCOPE OF |
| | WORK. |
| | |
| | 8) NOTE: PLEASE SEE THE " EQUIPMENT GROUNDING |
| | CONDUCTORS" FROM THEN METER CENTER MAINS TO THE UNITS |
| | ARE NOT LARGE ENOUGH PER 250.122. PLEASE SEE MIN SIZE |
| | SHALL BE #6. |
| | |
| | 9) NOTE: PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS. |
| | PLEASE SEE SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY |
| | CLOSE, PLEASE VERIFY. |
| | PLEASE SEE TABLES IN CHAPTER 9. |
| | |
| | 10) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO |
| | THE METER CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S |
| | ETC ARE OVER 200FT. |
| | |
| | 11) NOTE: PLEASE ALSO PROVIDE A WORST CASE VD ON |
| | APT/CONDO FEEDER(S). |
| | |
| | 12) NOTE: PLEASE KNOW THAT EACH PANEL IN EACH UNIT WILL |
| | BE REQUIRED TO BE UNDER A SEPARATE PERMIT FOR EACH |
| | UNIT, AS EACH UNIT IS INDIVIDUALLY OWNED. THIS TYPICAL |
| | PANEL DETAIL CAN BE ON 8/12 BY 11'S, HOWEVER TWO |
| | SIGNED, DATED AND SEALED COPIES FOR EACH APPLICATION |
| | WILL BE REQUIRED FOR PANEL CHANGE OUTS. |
| | 106.1.2, 106.1.3 ETC |
| | |
| | 13) NOTE: PLEASE CLARIFY LOAD CALCULATIONS ON MC WHICH |
| | INDICATE 450A OCP AND LOAD IS SHOWN AS 448A'S. PLEASE |
| | ONLY VERIFY. |
| | 215.5, 220. |
| | |
| | 14) NOTE: PLEASE BE SURE THE 2002 NFPA-70( NEC ) IS |
| | STATED ON PLANS. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 15) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN |
| | APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS |
| | THE VALUE SEEMS LOW. PLEASE KNOW VALUE PANEL FOR EACH |
| | UNIT CANE BE SUBTRACTED AS THESE WILL BE SEPARATE, |
| | HOWEVER ALL NEW FEEDERS FOR UNITS, FEEDERS FOR METER |
| | CENTERS AND NEW METER CENTERS SHALL BE INCLUDED. VALUE |
| | SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 108.3. |
| | |
| | 16) NOTE: PLEASE INDICATE AIC RATINGS FOR ALL MAINS , |
| | EQUIPMENT AND PANELS. PLEASE BE SURE TO INDICATE THE |
| | SELECTIVE COORDINATION AS REQUIRED. |
| | 110.9, 240.12 |
| | FBC106.1.2 ADMIN SECT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |