| 2007-01-29 12:43:16 | BUILDING REVIEW THIRD CHECKLIST: | | | | | | 1-CLARIFY WHAT 'S THE RELATIONSHIP BETWEEN VALMONT | | | STRUCTURES SPECIFICATIONS (PAGE 7 OF ENGINEERED PACKAGE | | | SUBMITTED) AND ENGINEERED DRAWING E-1.SEE SIZE OF | | | ANCHORS ETC.CLARIFY/REVISE AS REQUIRED. | | | | | | 2-VALMONT STRUCTURES SPECIFICATIONS PAGE 7: | | | EFFECTIVE PROJECTED AREA (EPA)DOESN'T WORK FOR | | | 140MPH.SEE DIMENSIONAL AND LOAD DATA. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|