Plan Review Notes
Plan Review Notes For Permit 06100782
Permit Number 06100782
Review Stop M
Sequence Number 1
Notes
Date Text
2006-11-21 08:11:12*** DENIED ***
 1) NEED SIZE OF RETURN AIR TRUNK LINE TO AHU.
  
 2) PROVIDE COMBUSTION AIR FOR GAS WATER HEATER IN
 CLOSET, PER 2004 FBC/R M1701.1.
  
 3) OPEN GRILL IN COVERED PATIO WILL NEED AN APPROVED
 EXHAUST HOOD, PER 2004 FBC/M 505.3.
  
 4) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 HOOD.
  
 5) SEECOPRE LINE SIZES ON MECHANICAL PLANS 3/8 AND
 1/8, DO YOU MEAN 1 1/8 ? PLEASE PLEASE CORRECT IN TWO
 PLACES SHOWING COPPER LINE SIZES OR SUBMIT
 MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.