| 2006-11-21 08:11:12 | *** DENIED *** | | | 1) NEED SIZE OF RETURN AIR TRUNK LINE TO AHU. | | | | | | 2) PROVIDE COMBUSTION AIR FOR GAS WATER HEATER IN | | | CLOSET, PER 2004 FBC/R M1701.1. | | | | | | 3) OPEN GRILL IN COVERED PATIO WILL NEED AN APPROVED | | | EXHAUST HOOD, PER 2004 FBC/M 505.3. | | | | | | 4) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | HOOD. | | | | | | 5) SEECOPRE LINE SIZES ON MECHANICAL PLANS 3/8 AND | | | 1/8, DO YOU MEAN 1 1/8 ? PLEASE PLEASE CORRECT IN TWO | | | PLACES SHOWING COPPER LINE SIZES OR SUBMIT | | | MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|