| Plan Review Notes For Permit 06100782 |
| Permit Number |
06100782 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-08 10:37:44 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | 2} SUBMIT PANEL SCHEDULES PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. ALL PANELS SO CALCULATIONS CAN BE | | | REVIEWED, AND BRANCH CIRCUIT AND OVERCURRENT PROTECTION | | | REQUIREMENT MAY BE REVIEWED FOR COMPLIANCE. | | | | | | 3}PROVIDE LOAD CALCULATIONS PER 220 SECTION I, | | | STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR | | | 220.SECTION III, OPTIONAL CALCULATIONS. IT WOULD APPEAR | | | THE LOAD AFTER DEMAND IS GREATER THAN THE SERVICE | | | PROVIDED. | | | | | | 4} GFI,S ARE REQUIRED FOR BATH RECEPTACLES PER | | | 210.8(A)(1), 2002 NEC. INDICATE ON PLANS. | | | | | | 5} BATHROOM RECEPTACLES (AT LEAST ONE) MUST BE WITHIN | | | 3' OF THE BASIN PER 210.52, SEE MASTER BATH. | | | | | | 6} THE MASTER AND GUEST BEDROOM NEED ADDED RECEPTACLES | | | TO COMPLY WITH 210.52(A)(1) &( 2), SEE REVIEWED SET FOR | | | EXAMPLE. | | | | | | 7} THE HALLWAY MUST HAVE ONE RECEPTACLE TO COMPLY WITH | | | 210.52(H). | | | | | | 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|