 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 2} SUBMIT PANEL SCHEDULES PER 408.4 NEC AND
 106.3.5.4(8) FBC. ALL PANELS SO CALCULATIONS CAN BE
 REVIEWED, AND BRANCH CIRCUIT AND OVERCURRENT PROTECTION
 REQUIREMENT MAY BE REVIEWED FOR COMPLIANCE.
  
 3}PROVIDE LOAD CALCULATIONS PER 220 SECTION I,
 STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR
 220.SECTION III, OPTIONAL CALCULATIONS. IT WOULD APPEAR
 THE LOAD AFTER DEMAND IS GREATER THAN THE SERVICE
 PROVIDED.
  
 4} GFI,S ARE REQUIRED FOR BATH RECEPTACLES PER
 210.8(A)(1), 2002 NEC. INDICATE ON PLANS.
  
 5} BATHROOM RECEPTACLES (AT LEAST ONE) MUST BE WITHIN
 3' OF THE BASIN PER 210.52, SEE MASTER BATH.
  
 6} THE MASTER AND GUEST BEDROOM NEED ADDED RECEPTACLES
 TO COMPLY WITH 210.52(A)(1) &( 2), SEE REVIEWED SET FOR
 EXAMPLE.
  
 7} THE HALLWAY MUST HAVE ONE RECEPTACLE TO COMPLY WITH
 210.52(H).
  
 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  