2007-01-04 14:35:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB CHAPTER 3.
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 6.)PRODUCT APPROVALS REQUIRED FOR THE EXTERIOR DOOR
 (CABANA BATH) AND THE FIXED GLASS WINDOW.
  
 7.)SHOW ATTIC ACCESS LOCATION FBC R807.1.
  
 8.)SHOW VENTILATION IN COMPLIANCE WITH FBC R806.
  
 9.)SMOKE DETECTORS REQUIRED FBC R313.1.
  
 10.)SHOW DIMENSIONS FROM GRADE TO BOTTOM OF FOOTING
 AND TOP OF SLAB.
  
 11.)SHOW DRAINAGE FBC R401.3.
  
 12.)A7, FOUNDATION NOTE 3, REFERS TO THE INCORRECT
 ACI REFERENCE, FBC 35.
  
 13.)A7, WOOD TRUSSES, NOTE REFERS TO INCORRECT
 ANSI/TPI REFERENCE, FBC35.
  
 14.)SHOW EMERGENCY EGRESS FOR PROPOSED NEW BEDROOMS,
 FBC R310.
  