| 2006-10-24 14:30:29 | ******** UNSAT ********** |
| | |
| | 1) NOTE: PLEASE PROVIDE A PANEL SCHEDULE WHICH |
| | INDICATES ALL OF THE REQUIRED MINIMUM CIRCUITS. PLEASE |
| | BE SPECIFIC FOR CIRCUITS TO ALL AREAS AND ROOMS. PLEASE |
| | SEE FOR INSTANCE ONLY ONE CIRCUIT IS BEING SHOWN IN THE |
| | LOAD CALCULATIONS FOR THE BATH(S)RMS). |
| | PLEASE INDICATE FOLLOWING : IE: BED RM #2 LTS, MASTER |
| | BEDRM RECETPS, KITCHEN LTS, ETC ETC. |
| | PLEASE INDICATE ALL CONDUCTOR SIZES AND CORRELATE WITH |
| | OCP DEVICES. |
| | 240.4,408.4, 310.16 |
| | |
| | 2) NOTE: PLEASE SEE NOTES ON PLANS STILL MENTIONS AFCI |
| | PROTECTION ONLY FOR RECEPTS. WE ARE UNDER THE 2002 NEC. |
| | 210.12B |
| | PLEASE BE SURE TO LIST ALL AS REQUIRED PER CODE ON THE |
| | SAME PANEL SCHEDULE WHICH IS REQUIRED PER NOTE #1. |
| | |
| | 3) NOTE: PLEASE SEE 210.8A6 FOR ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE. |
| | |
| | 4) NOTE: PLEASE SEE 210.52C3/210.8A6 FOR MISSING |
| | RECEPT. |
| | |
| | 5) NOTE: PLEASE SEE NOTES ON PLANS WHICH MENTIONS FUSED |
| | DISCONNECT FOR SERVICE, YET SERVICE DOES NOT INDICATE |
| | THIS . PLEASE CORRELATE. |
| | 230.70, 230.70. |
| | PLEASE SEE PLANS ARE MISSING THE LOCATION OF THE |
| | SERVICE AND PANEL. 230.70,240.24 |
| | CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| | PLANS FOR THE DESIGN AT THIS TIME. 2002 NFPA-70, 2002 |
| | NFPA-72. |
| | |
| | 7) NOTE: PLEASE INDICATE THE REQUIRED DISCONNECT FOR |
| | THE WATER HEATER 422.31. |
| | |
| | 8) NOTE: PLEASE SEE FS 713.13(2) AS THE NOTICE OF |
| | COMMENCMENT WHICH WAS SUBMITTED WITH PERMITTED |
| | APPLICATION WAS ALREADY EXPIRED WHEN IT WAS SUBMITTED. |
| | PLEASE SEE SECTION WHICH STATES WORK SHALL COMMENCE |
| | WIHTIN 90DAYS OF RECORDING SUCH NOC OR THE NOC SHALL |
| | BECOME VOID AND IS NO LONGER VALID. |
| | THE RE-RECORDED NOC IS ONLY REQUIRED AT THE TIME OF |
| | PICKING UP PERMIT ONCE ISSUED. |
| | |
| | |
| | |
| | *** NOTE: PLEASE SEE FLORIDA STATUTES 481.221(6). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |