| 2006-11-22 16:38:43 | BUILDING REVIEW 2ND CHECKLIST: |
| | 1- SUBMITTED ENGINEERING PLANSDON'T PROVIDE ALL |
| | STRUCTURALINFORMATION REQUIRED. SEE RESTORATION |
| | PROPOSAL LETTER FROM BUILDINGCONTRACTOR. DRAWINGS TO |
| | INCLUDE: |
| | * INSTALLATION OF JACKS TO SUPPORT ROOF. |
| | **CLARIFY WHY THE ROOFNEEDS TO BE SUPPORTED AND |
| | PROVIDE COMPLETE SPECIFICATIONS FOR STRUCTURAL WORK TO |
| | BE PERFORMED. |
| | ***REMOVAL OF 2X6 STUD WALL (NORTH).PROVIDE COMPLETE |
| | STRUCTURAL SPECS FOR NEW WALL, INCLUDING SHEATHING |
| | FASTENING SIZE AND SPACING AND STUCCO THICKNESS. |
| | ****ADDRESS CONCRETE BLOCK CRACKS AND SPECIFIC SPECS |
| | FOR REPAIRS. |
| | |
| | 2- ENGINEERED DRAWINGS: |
| | A) DON'T MATCH KEY PLAN SUBMITTED FOR WINDOW SIZE. |
| | REVISE EITHER ONE AS REQUIRED TO SHOW ACTUAL |
| | CONDITIONS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) CLEARLY IDENTIFY TYPE OF CONSTRUCTION. IS THIS |
| | TYPE V A OR B?SEE SEC. 602 FBC 2004. |
| | |
| | C) REVISE DESIGN CRITERIA REFERENCE. THERE ARE NOT |
| | SECTIONS R4403.5 ANDR4403.9. |
| | |
| | D) NEED TO PROVIDE FIRM'S CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | |
| | E) SPECIFY HOW ARE EXISTING JOISTS FASTENED TO NEW |
| | FOOTING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | F) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR NEW |
| | 1/2" WEDGE ANCHORS SPECIFIED ON SUPPLEMENTAL FOOTING. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- REVISE ENGINEER DESIGN PRESSURES CALCULATIONS: |
| | A) IMPORTANCE FACTOR AND CATEGORY ARE INCORRECT. SEE |
| | ASCE-02 FOR CORRECT INFORMATION ACCORDING TO BUILDING |
| | TYPE. |
| | |
| | B) IDENTIFY EACH WINDOW AND DOOR OPENING WITH |
| | CORRESPONDING DESIGN PRESSURES. ALSO, IDENTIFY IF |
| | OPENING IS LOCATED AT END OR INTERIOR ZONE. SEC. 1609 |
| | FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) NEED TWO COPIES WITH ENGINEER'S ORIGINAL SEAL AND |
| | SIGNATURE AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES. ONLY ONE PROVIDED. |
| | |
| | D) NEED TO PROVIDEENGINEERING FIRM CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | |
| | E) NEED ENGINEER'SNAME AS REQUIRED BY F.A.C. SEC. |
| | 61G15-23.002. |
| | |
| | 4- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN AND COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED COPY AND PROVIDE ALL SPECIFIC |
| | INFORMATION FOR PROPOSED INSTALLATION. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL FOR ALL SIMPSON OR USP |
| | CONNECTORS IF THEY ARE SPECIFIED ON ENGINEERING PLANS. |
| | ***AND ENGINEER TO REVIEW AND APPROVE THEM AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- OWES $1733.46 FOR 4X FEE FOR WORK WITHOUT PERMIT RED |
| | TAG. |
| | |
| | 7- NEED TO APPLY FOR PERMITS FOR THE OTHER TRADES AS |
| | REQUIRED. |
| | |