| 2006-11-08 15:51:59 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 2- PROVIDE COMPLETE ENGINEERING PLANS SHOWING ALL |
| | PROPOSED WORK. FOLLOW FBC 2004 AND FLORIDA RESIDENTIAL |
| | CODE 2004 RESPECTIVELY. LETTER FROM FLAHERTY ASSOCIATES |
| | INC., ENGINEERING FIRM, ONLY STATES THAT THEY WERE |
| | RETAINED TO DO THE DRAWINGS.PLAN REVIEW CAN'T BE |
| | PERFORMED IF DRAWINGS ARE NOT SUBMITTED FOR REVIEW. |
| | |
| | 3- PROVIDE KEY PLAN SHOWING SIZE OF WINDOWS TO VERIFY |
| | BEDROOM'S EGRESS REQUIREMENTS. SEC. R310.1 2004 FLORIDA |
| | RESIDENTIAL CODE AND SEC. 505.1 OF 2004 EXISTING |
| | BUILDING. |
| | |
| | 4- STORM SHUTTERS:PROVIDE KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. SEE ATTACHED INSTALLATION SCHEDULE CITY |
| | SAMPLE AND PROVIDE ALL REQUIRED INFORMATION. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY |
| | RULE 9B-72 FOR: |
| | A) STORM SHUTTERS. ONLY ONE COPY SUBMITTED. |
| | B) SINGLE HUNG WINDOWS. ONLY ONE COPY SUBMITTED. |
| | ***NOTE: DRAWING FROM AMERICAN CRAFTSMAN WINDOWS IS NOT |
| | A PRODUCT APPROVAL. NEED TO PROVIDE COMPLETE PRODUCT |
| | APPROVAL IF USING THIS TYPE OF WINDOW. |
| | C) DOORS. NONE SUBMITTED. |
| | D) ALL SIMPSON OR USP STRUCTURAL CONNECTORS |
| | SPECIFIED ON THE ENGINEER'SPLANS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | ***NOTE; REQUIREMENT IS TO REVIEW AND APPROVE IN |
| | WRITING NOT SIGN AND SEAL THEM. |
| | |
| | 7- THERE WAS SOME CONSTRUCTION GOING ON WITHOUT PERMIT. |
| | CONTRACTOR WAS RED TAGGED ON 10/30/06 BY INSPECTOR FOR |
| | 4X PERMIT FEES.SEE ATTACHED COPY. OWES $1733.46. THIS |
| | INCLUDES 4X PERMIT FEES PLUS UPDATED VALUATION. |
| | CONTRACTOR LETTER STATES WORK TO BE PERFORMED FOR |
| | $27,300 NOT 23,000. |
| | ***NOTE:APPLY FOR PLUMBING , ELECTRICAL, MECHANICAL |
| | AND ROOFING PERMITS IF SUCH WORK IS GOING TO BE |
| | PERFORMED. |
| | |
| | 8- ACCORDING TO CONTRACTOR'S SCOPE OF WORK LETTER THERE |
| | WILL BE 2 COATS OF STUCCO APPLIED.NEED TO PROVIDE 3 |
| | COATS AS REQUIRED BY SEC. 7.1.6 AND TABLE 1 OF ASTM |
| | C-926.SEE TABLE 1 ON ASTM C-926 FOR TOTAL THICKNESS |
| | REQUIRED. |
| | |