Plan Review Notes For Permit 06100743
Permit Number 06100743
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-20 14:14:14*****DENIED*****
  
  
  
 1.IN ADDITION TO THE 2003 EDITION OF NFPA 101,
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION - SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST
 AND DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 4.THE BUILDING'S FIRE PROTEDCTION SYSTEMS SHALL BE
 MAINTAINED OPERATIONAL AT ALL TIMES.
  
 5.HOW MANY FLOORS WILL BE DONE AT A TIME?IF THE
 FLOOR(S) IS/ARE BE OCCUPIED DURING THE SCOPE OF WORK,
 HOW WILL THE REQUIRED MEANS OF EGRESS INCLUDING DOORS,
 WALKWAYS, STAIRS, ETC BE MAINTAINED TO ENSURE
 REASONABLE LIFE SAFETY?
  
 6.IF THE FIRE ALARM OR FIRE SPRINKLER SYSTEM ARE TO
 BE MODIFIEDDUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 7.INDICATE INTERIOR FINISH FOR WALLS AND CEILINGS.
 CLASS A OR B IS REQUIRED IN THE MEANS OF EGRESS AREAS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  