| Plan Review Notes For Permit 06100743 |
| Permit Number |
06100743 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-14 07:06:02 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC | | | DESIGNATIONS AS SPECIFIED IN FBC TABLE 601. SPECIFY A | | | OR B. | | | | | | 3) THE DOORS TO ONE SET OF EGRESS STAIRS ARE NOT SHOWN | | | ON THE FLOOR PLANS ON SHEETS A2-A7. | | | | | | 4)EGRESS DOORS ARE REQUIRED TO SWING IN THE DIRECTION | | | OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 | | | OR MORE PERSONS PER FBC 1008.1.2. | | | | | | 5) PROVIDE THE FLAME SPREAD AND SMOKE DEVELOPED INDEXES | | | FOR THE WOOD VENEER PANELS IN THE CORRIDORS AT THE | | | ELEVATORS. SEE FBC 803.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|