| 2007-03-04 10:34:08 | ***PROVISO/REVISON*** |
| | |
| | 1) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING |
| | CONDUCTORS* SHOWN ON THE LINE SIDE OF THE METER AND |
| | MAINS ARE NOT TO BE INSTALLED AS THIS WOULD PARALLEL |
| | THE NEUTRAL FOR OBJECTIONABLE CURRENTS. |
| | PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING |
| | CONDUCTORS* ARE INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 2) NOTE: PLEASE BE SURE TO UPDATE PANEL SCHEDULES AND |
| | PLANS TO SHOW ALL NEW CIRCUITING TO THE NEW PANELS AND |
| | ALL CIRCUITS IN PANELS TO EACH OF THESE |
| | LOCATIONS/ROOMS. |
| | PLEASE SEE SECTION OF COMMENTARY WHICH REQUIRES ALL |
| | CIRCUITS TO BE SPECIFIC TO AREAS AND ROOMS IN WHICH |
| | THEY FEED. THE FOLLOWING IS TAKEN DIRECTLY FORM THAT |
| | COMMENTARY. |
| | ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND |
| | STAMPING. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |