| Plan Review Notes For Permit 06100734 |
| Permit Number |
06100734 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-01 12:20:19 | *** DENIED *** | | | 1) SEE PLANS PG. AC-2.1, HP-E4 NEW 10X8 FRESH AIR DUCT | | | THROU FIRE WALL AT PORTFOLIO MANAGER ROOM #163 , NEEDS | | | A FIRE DAMPER, PER 2004 FBC/M 607.5.1. | | | | | | 2) SEE PLANS PG. AC-2.1, NEW 6" FLEX DUCT THROU FIRE | | | WALL FROM CORRIDOR #2 TO CORR. #3A NEEDS A FIRE DAMPER, | | | PER 2004 FBC/M 607.5.1. | | | | | | 3) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|