| 2006-10-30 07:50:52 | ******** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECT ADDRESS |
| | OF JOB AT 4100 OKEECHOBEE BLVD AS WELL AS 3111 S |
| | DIXIE. |
| | |
| | PLEASE ALSO SEE THE JURISDICTION IS NOT IN PALM BEACH |
| | COUNTY. JOB-SITE LOCATION IN THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE FAC |
| | 61G1-16.004 AND FS 481.219. |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER/ FIRM |
| | LICENSE NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| | REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101 . |
| | **AS STATED ON PLANS, THE "LATEST EDITION " WHICH IS |
| | AVAIABLE IS NOT YET ADOPTED BY THE STATE> (NEC). |
| | |
| | 4) NOTE; PLEASE SEE AREAS WHICH ARE SHOWN AS COMMON |
| | AREA CORRIDORS YET SHOW ELECTRICAL FOR RECEPT AND HVAC |
| | BEING FED FROM A TENANT SPACE. PLEASE KNOW, NO COMMON |
| | AREAS MAY BE FED FROM FROM AN TENANT OCCUPANCY. 210.25, |
| | 90.4. |
| | |
| | 5) NOTE: PLEASE SEE PANEL SCHEDULE FOR "H2" SHOWS OTHER |
| | ELECTRICAL HOWEVER COULD NOT LOCATE WHAT OR WHERE THESE |
| | ITEMS ARE?? |
| | PLEASE ALSO SEE LOADS ON THIS PANEL IS SHOWN AS XXXXX |
| | (BLANK), PLEASE COMPLETE. |
| | 220, 215.5, |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE: PLEASE SEE RISER AND EXPLAIN HOW FEEDERS FROM |
| | FPL ARE ROUTED TO THE GUTTER. RISER SEEMS TO SHOW THE |
| | CT/METER ON THE LOAD SIDE OF THE MDP??? |
| | PLEASE CLARIFY AND REVISE RISER. AS SHOWN DOES NOT |
| | CORRELATE WITH MIN FPL SERVICE STANDARDS OR NEC. 230. |
| | |
| | 7) NOTE: PLEASE SEE PANEL INDICATE CIRCUITING FOR NEW |
| | ROOMS. |
| | PLEASE SEE PANEL "G" IS BEING SHOWN BEING SHOWN AS 125A |
| | RATED, YET RISER SHOWS A 150A MAIN DISCONNECT FEEDING |
| | SAID PANEL. |
| | PLEASE SEE 240, 230 ETC |
| | |
| | 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW |
| | DISCONNECTS ARE SHOWN ON RISER. PLEASE SEE 110.9, |
| | 240.12 |
| | |
| | 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3, 230.42 |
| | |
| | 10) NOTE: PLEASE BE SURE ALL SEALS ARE RAISED, CLEAR |
| | AND VISABLE WITH ALL INFORMATION AS REQUIRED ON SAID |
| | SEAL. |
| | PLEASE SEE SOME ARE NOT VISABLE EVEN WHEN SHADING WITH |
| | PENCIL. |
| | FS471.025 |
| | PLEASE BE SURE THEY ARE ALSO SIGNED WITH LEGAL |
| | SIGNATURE. |
| | |
| | 11) NOTE: PLEASE SEE FBC 13-101.1.3, METHOD "A" MAY NOT |
| | BEUSED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |