| Plan Review Notes For Permit 06100725 |
| Permit Number |
06100725 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-01 15:38:36 | BUILDING REVIEW CHECKLIST: | | | 1- PROVIDE KEY PLAN SHOWING LOCATION OF OPENINGS. | | | DRAWING SUBMITTED IS NOT A KEY PLAN BUT AN ELEVATION OF | | | OPENINGS. ALSO, CLARIFY IF OPENINGS TO BE PROTECTED ARE | | | THE DOORS, THEN HOW ARE THE WINDOWS SHOWN ON ELEVATION | | | BEING PROTECTED. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 2- CLARIFY IF USING FLORIDA PRODUCT APPROVAL FL5345 | | | WITH DRAWINGS #05-517 OR DADE COUNTY NOANOA | | | #05-0713.03. BOTH PRODUCT APPROVALS WERE SUBMITTED. | | | NEED TO SUBMIT COMPLETE INFORMATION FOR ONLY ONE | | | PRODUCT APPROVAL. DON'T MISMATCH ONE WITH THE OTHER. IF | | | USING DADE COUNTY NOA, THEN PROVIDE THE MISSING | | | DRAWINGS. | | | | | | 3- INSTALLATION SCHEDULE SUBMITTED: | | | A) ANCHOR SPACING DOESN'T WORK. SEE SHEET5 OF 6 OF | | | DRAWING 05-517 SUBMITTED. | | | B) MIN. EDGE DISTANCE OF 1.25" DOESN'T WORK. SEE | | | SHEET 5 OF 6 OF DRAWING 05-517 SUBMITTED. | | | C) CLEARLY IDENTIFY SPECIFIC ANCHOR TO BE USED. SEE | | | SHEET 5 OF 6 OF DRAWING 05-517 SUBMITTED AND DESCRIBE | | | SPECIFIC ANCHOR.THERE ARE DIFFERENT TYPES OF TAPCONS | | | ANDWHAT IS A LEAD ANCHOR?. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|