2007-01-22 17:53:29BUILDING REVIEW CHECKLIST:
 1-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TOFBC 2004. PRODUCT APPROVALS FOR
 HORIZONTAL SLIDER, SINGLE HUNG WINDOWS AND CASEMENT
 WINDOWS WERE NOT REVIEWED AND APPROVED.
  
 2- STORM SHUTTERS:
 A) ACCORDING TO PRODUCT APPROVALDRAWING #05-279
 PAGE 13 OF 21 THE MAXIMUM SHUTTER HEIGHT IS 4'-6".SEE
 TABLE ON BOTTOM CENTER OF PAGE.THERE ARE SOME
 OPENINGS THAT EXCEED THIS DIMENSION. THEREFORE, IT
 CAN'T BE USED ON THOSE OPENINGS.
  
 B) MINIMUM EDGE DISTANCE IS 3.5".SEE ENGINEERED
 DRAWINGS. THERE ARE SOME OPENINGS SHOWING 2.5" EDGE
 DISTANCE. REVISE AS REQUIRED.
  
 C) THERE IS NOT INFORMATION GIVEN FOR PROPOSED
 INSTALLATION OF STORM PANELS AT FRONT DOOR. ONLY THE
 PRODUCT APPROVAL WAS SUBMITTED. PROVIDE COMPLETE
 INFORMATION.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- ENERGY CALCULATIONS;
 A) WHO PREPARED THE CALCULATIONS. THIS SECTION WAS
 LEFT BLANK.
  
 B)ARCHITECT SIGNING AND SEALING AT BOTTOM OF FORM
 TO PROVIDE ALL HIS INFORMATIONAS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
  
 C) PERMIT NUMBER WRITTEN ON TOP OF FORM DOESN'T
 CORRESPOND TO PERMIT NUMBER FOR THIS ADDITION. REVISE
 AS REQUIRED.
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED. SEE SEC. 713.13
 FLORIDA STATUTES. PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT.
  