Plan Review Notes
Plan Review Notes For Permit 06100722
Permit Number 06100722
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-06 09:01:42UNSAT
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE:
  
 1. IN BATH #2 THE TUB AND SHOWER NEEDS A VENT PER
 FBC-2004 PLUMBING SECTION 909.1 WET VENTS.
  
 2. IN BATH #2 THE FLOOR DRAIN INDICATED NEEDS A TRAP
 PRIMER PER FBC-2004 PLUMBING SECTION 1002.4 TRAP SEAL.
  
 3. IN THE KITCHEN THE AIR ADMITTANCE VALVE IS
 INDICATED IN THE WRONG PLACE PER FBC-2004 PLUMBING
 SECTION 917.4 LOCATION. PLEASE INDICATE THE DISH WASHER
 DRAIN ON THE RESUBMITTAL.
  
 4. IN THE MASTER BATH THE SHOWER NEEDS A VENT PER
 FBC-2004 PLUMBING SECTION 909.1 WET VENTS.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  