| Plan Review Notes For Permit 06100722 |
| Permit Number |
06100722 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-06 09:01:42 | UNSAT | | | REFERENCE: FBC-2004 PLUMBING | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE | | | COMPLIANCE: | | | | | | 1. IN BATH #2 THE TUB AND SHOWER NEEDS A VENT PER | | | FBC-2004 PLUMBING SECTION 909.1 WET VENTS. | | | | | | 2. IN BATH #2 THE FLOOR DRAIN INDICATED NEEDS A TRAP | | | PRIMER PER FBC-2004 PLUMBING SECTION 1002.4 TRAP SEAL. | | | | | | 3. IN THE KITCHEN THE AIR ADMITTANCE VALVE IS | | | INDICATED IN THE WRONG PLACE PER FBC-2004 PLUMBING | | | SECTION 917.4 LOCATION. PLEASE INDICATE THE DISH WASHER | | | DRAIN ON THE RESUBMITTAL. | | | | | | 4. IN THE MASTER BATH THE SHOWER NEEDS A VENT PER | | | FBC-2004 PLUMBING SECTION 909.1 WET VENTS. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | |
|