Plan Review Notes
Plan Review Notes For Permit 06100722
Permit Number 06100722
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-03 10:08:07 
  
 INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE CONDUIT AND CONDDUCTOR SIZE AND TYPE FOR
 THE SERVICE RISER. 215.5.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. FOR PANEL LISTED
 AS EMERGENCY. THERE ARE NO BRANCH CIRCUITS SHOWN FOR
 THIS 20 CIRCUIT PANEL.
  
 3} PLEASE SHOW LOAD CALCULATIONS PER 220.3SECTION I
 STANDARD METHOD OR OPTIONAL METHOD SECTION III.
  
 4} 210.52(C)(1) WALL COUNTER SPACES. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTER SPACE
 THAT IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM
 A RECEPTACLE OUTLET IN THAT SPACE.
  
 5} 210.8(A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (1) BATHROOMS
  
 6} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING.
  
 7} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. SEE FRONT
 BEDROOM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH