| 2006-11-03 10:08:07 | |
| | |
| | INCOMPLETE INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} INDICATE CONDUIT AND CONDDUCTOR SIZE AND TYPE FOR |
| | THE SERVICE RISER. 215.5. |
| | |
| | 2} PROVIDE A PANEL SCHEDULE PER 408.4. FOR PANEL LISTED |
| | AS EMERGENCY. THERE ARE NO BRANCH CIRCUITS SHOWN FOR |
| | THIS 20 CIRCUIT PANEL. |
| | |
| | 3} PLEASE SHOW LOAD CALCULATIONS PER 220.3SECTION I |
| | STANDARD METHOD OR OPTIONAL METHOD SECTION III. |
| | |
| | 4} 210.52(C)(1) WALL COUNTER SPACES. A RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH WALL COUNTER SPACE |
| | THAT IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| | IS MORE THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM |
| | A RECEPTACLE OUTLET IN THAT SPACE. |
| | |
| | 5} 210.8(A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE |
| | LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL HAVE |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | (1) BATHROOMS |
| | |
| | 6} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING. |
| | |
| | 7} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. SEE FRONT |
| | BEDROOM. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |