| 2006-11-09 19:01:02 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE SOIL TEST REPORT. |
| | |
| | 2- PROVIDE FLORIDA PRODUCT APPROVAL AS REQUIRED BY RULE |
| | 9B-72 FOR: |
| | A) GARAGE DOOR. NEED TO PROVIDE CLEAR AND LEGIBLE |
| | DRAWINGS. ONE SUBMITTED IS NOT LEGIBLE. |
| | B) FRONT DOOR. |
| | C) FRENCH DOORS WITH AND WITHOUT SIDELITES AS SHOWN |
| | ON PLANS.DADE COUNTY NOA SUBMITTED IS EXPIRED AND THE |
| | FLORIDA PRODUCT APPROVAS ARE MISSING THE DRAWINGS. NEED |
| | COMPLETE AND CURRENT PRODUCT APPROVAL PACKAGE. |
| | D) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS. |
| | E) ROOF SHINGLES.ACCORDING TO DADE COUNTYPRODUCT |
| | APPROVAL WEBSITE NOA 02-1209.10 SUBMITTED THE FILE IS |
| | CLOSED. NEED TO PROVIDE CURRENT NOA. |
| | F) PRECAST LINTELS. NOA 03-0605.04 SUBMITTED IS FOR |
| | 4", 6" AND 12" LINTELS. NEED PRODUCT APPROVAL FOR 8" |
| | LINTELS AS SPECIFIED ON PLANS. |
| | G) STORM SHUTTERS. NEED COMPLETE PRODUCT APPROVAL. |
| | H) LAUNDRY EXTERIOR DOOR. |
| | |
| | 3- DESIGNEROF RECORD TO REVIEW AND APPROVE IN |
| | WRITTING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- STORM SHUTTERS: |
| | A) PROVIDE COMPLETE PRODUCT APPROVAL PACKAGE. |
| | B) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED CITY SAMPLE OF INSTALLATION SCHEDULE AND |
| | PROVIDE ALL THE REQUIRED INFORMATION. |
| | |
| | 5- ENERGY CALCULATIONS: |
| | A) CLARIFY WHY THE CONDITIONED FLOOR AREA IN ITEM #5 |
| | IS DIFFERENT ON ITEM #10. REVISE AS REQUIRED. |
| | |
| | B) IF USING CEILING FANS CREDIT, THEN NEED TO |
| | SPECIFY FAN SIZES IN ALL ROOMS AS REQUIRED BY TABLE |
| | 13-607.1.A.1 OF FBC 2004. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 6- PROVIDE DRAINAGE PLANS INDICATING FLOW OF WATER AS |
| | REQUIRED BY SEC. R401.3 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- TRUSSES WILL NEED TO BE SUBMITTED FOR REVIEW AS |
| | REQUIRED BY SECTION R802.10 2004 FLORIDA RESIDENTIAL |
| | CODE. DESIGNER OF RECORD TO REVIEW AND APPROVE THEM |
| | BEFORE SUBMITTAL TO THIS OFFICE. |
| | |
| | 8- DRAWING #1: |
| | A) THIS IS NOT "LEVEL 2" ALTERATION. REVISE NOTE AS |
| | REQUIRED. SEE CHAPTER 3 OF 2004 EXISTING BUILDING FOR |
| | ALTERATION LEVEL DEFINITIONS. |
| | |
| | B) SPECIFY SAFETYGLASS AT EXISTING BATH WINDOW AND |
| | AT MASTER BATH ROMAN TUB AS REQUIRED BY SEC. R308.4 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) SPECIFY CALCULATED DESIGN PRESSURES FOR GARAGE |
| | DOOR. |
| | |
| | 9- ROOF PITCH IS 3.375:12. NEED TO SPECIFY DOUBLE |
| | DOUBLE LAYER OF UNDERLAYMENT AS REQUIRED BY SEC. |
| | R905.2.7 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- TYPICAL WALL SECTION. SPECIFY FIREBLOCKING AS |
| | REQUIRED BY SEC. R602.8 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (5610805-6712 |