Plan Review Notes
Plan Review Notes For Permit 06100720
Permit Number 06100720
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-01 11:52:41UNSAT
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1,
 FLORIDA ADMINISRTATIVE CODE, FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE.
  
 1.FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 (NOTE: NUMBER TWO (2) IS MISSING FROM THE TITLE
 BLOCK.)
  
 2. FAC-CODE-61G1-16001 ARCHITECT'S AND
 INTERIOR DESIGNER'S SEAL: (NOTE: THE SEAL IMPRESSION IS
 WEAK AND NOT LEGIBLE)
  
 3. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE PROVIDE A COMPLETE FLOOR
 PLAN OF SAID RESIDENCE THAT CORRELATES WITH THE
 SANITARY RISER DIAGRAM. THE SANITARY RISER DIAGRAM
 INDICATES A NEW LAV THAT IS NOT INDICATED ON THE FLOOR
 PLAN. ALSO THERE IS A WATER CLOSET AND TUB WITH NO LAV
 INDICATED ON THE SANTARY RISER DIAGRAM THAT IS NOT
 INDICATED ON THE FLOOR PLAN. THIS IS CONFUSING, NOT TO
 MENTION UNSANITARY BY NOT HAVING A PLACE TO WASH HANDS
 AFTER USING WATER CLOSET. PLEASE CORRECT DRAWINGS FOR
 THE RESUBMITTAL.
  
 4. PER FBC-2004 PLUMBING, SECTION 704.2: THE SIZE OF
 THE DRAINAGE PIPING SHALL NOT BE REDUCED IN SIZE IN THE
 DIRECTION OF FLOW.
  
 5. PER FBC-2004 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING
 METHODS SPECIFIED IN THIS CHAPTER. (NOTE: THE LAVAND
 NEW LAV ARE NOT VENTED.)
  
 6. PER FBC-2004,PLUMBING, SECTION 905.3
 VENT CONNECTIONS TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE.
  
 7. PER FBC-2004 PLUMBING, SECTION 802.1.6 DOMESTIC
 DISHWASHING MACHINES: DOMESTIC DISHWASHING MACHINE
 SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. (NOTE: THE
 DISHWASHER CONNECTION INDICATED ON DRAWINGS IS WRONG,
 PLEASE SEE CORRECTED DRAWING FOR RESUBMITTAL.)
  
 8. THE WATER CLOSETS INDICATED ON THE DRAWING INDICATE
 TRAPS. THIS IS WRONG PER FBC-2004 PLUMBING, SECTION
 1002.1 FIXTURE TRAPS: A FIXTURE SHALL NOT BE DOUBLE
 TRAPPED. (NOTE: A WATER CLOSET HAS AN INTREGRAL TRAP
 WHICH MEANS ONE DOES NOT NEED TO BE PROVIDED.)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  