| 2006-10-30 15:13:27 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) | | | AND 210.52 (A) (2). | | | | | | 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). | | | | | | 5} 210.52(E) OUTDOOR OUTLETS. FOR A ONE-FAMILY DWELLING | | | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE | | | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT | | | GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2 FT) ABOVE | | | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE | | | DWELLING. SEE 210.8(A)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|