2006-11-03 12:13:41****DENIED***
  
 1.SINCE THE SCOPE OF THE WORK IS GREATER THAN
 $2500.00, THE APPLICANT SHALL FILE WITH THE AHJ EITHER
 A RECORDED NOTICE OF COMMENCEMENT OR A NOTORIZED
 STATEMENT THAT THE NOTICE OF COMMENCEMENT HAS BEEN
 FILED FOR RECORDING, ALONG WITH A COPY THEREOF.
  
 2.THE SUBMITTED PLANS AND HYDRAULIC CALCULATIONS
 SHEETS SHOULD REFLECT THE LOCATION WHERE THE ACTUAL
 WORK IS BEING DONE.
  
 3.A SAFETY MARGIN OF AT LEAST 5.0 PSI SHOULD BE SHOWN
 IN THE HYDRAULIC CALCULATIONS.
  
 4.NFPA 13, 2002 EDITION, SHALL BE REFERENCED.
  
 **REMINDERS**
  
 5.WATERFLOW ACTIVATION SHALL INTIATE A GENERAL ALARM
 WITHIN 45 TO 60 SECONDS.
  
 6.SPRINKLER SYSTEM IS TO BE MONITORED.
  
 7.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
 COORDINATE WITH THE GENERAL AND/OR FIRE ALARM CONTRATOR
 BY FINAL SPRINKLER/FIRE ALARM INSPECTION.
  
 **TO EXPEDITE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.**
  