| Notes |
| Date |
Text |
| 2006-11-03 12:13:41 | ****DENIED*** | | | | | | 1.SINCE THE SCOPE OF THE WORK IS GREATER THAN | | | $2500.00, THE APPLICANT SHALL FILE WITH THE AHJ EITHER | | | A RECORDED NOTICE OF COMMENCEMENT OR A NOTORIZED | | | STATEMENT THAT THE NOTICE OF COMMENCEMENT HAS BEEN | | | FILED FOR RECORDING, ALONG WITH A COPY THEREOF. | | | | | | 2.THE SUBMITTED PLANS AND HYDRAULIC CALCULATIONS | | | SHEETS SHOULD REFLECT THE LOCATION WHERE THE ACTUAL | | | WORK IS BEING DONE. | | | | | | 3.A SAFETY MARGIN OF AT LEAST 5.0 PSI SHOULD BE SHOWN | | | IN THE HYDRAULIC CALCULATIONS. | | | | | | 4.NFPA 13, 2002 EDITION, SHALL BE REFERENCED. | | | | | | **REMINDERS** | | | | | | 5.WATERFLOW ACTIVATION SHALL INTIATE A GENERAL ALARM | | | WITHIN 45 TO 60 SECONDS. | | | | | | 6.SPRINKLER SYSTEM IS TO BE MONITORED. | | | | | | 7.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. | | | COORDINATE WITH THE GENERAL AND/OR FIRE ALARM CONTRATOR | | | BY FINAL SPRINKLER/FIRE ALARM INSPECTION. | | | | | | **TO EXPEDITE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.** | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|