Plan Review Notes For Permit 06100695
Permit Number 06100695
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-09 07:33:37BUILDING PLAN REVIEW
 PERMIT: 06100696UNIT# 1
 06100693UNIT# 2
 06100695UNIT# 3
 06081555UNIT# 4
 ADD: 255 EVERNIA ST
 UNITS MU1-MU4
 CONT: INPROSFL, INC
 TEL: (954)2020500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3)2ND REQUEST,SINCE EACH UNIT WILL REQUIRE ITS OWN
 PERMIT APPLICATION,A NOTICE OF
 COMMENCEMENT WILL ALSO NEED TO BE
 RECORDED AT THE CLERK OF THE COURT.
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6A) COMPLIED.
  
 6B)2ND REQUEST, USE AND OCCUPANCY, IN ACCORDANCE WITH
 THE PROVISIONS OF SECTION 302.1.FBC.
  
 6C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. PLANS INDICATE TYPE V-PROTECTED TABLE 500,
 SEE THE HEIGHT AND AREA REQUIREMENTS TABLE 503, THIS IS
 FOR THE ENTIRE BLDG, HIGHRISE!!!!!
  
 6D)TO BE DETERMINED @ TENANT BUILD OUT.
  
 6E) COMPLIED.
  
 6F) COMPLIED.
  
 7)2ND REQUEST, THE STRUCTURAL SHEETS DO
 NOT PROVIDE THE WIND DESIGN PERAMETERS
 THATWILLIAM COOK P.E. DESIGNED TOO.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 PLEASE PROVIDE THE POSITIVE/ NEGATIVE PRESSURESFOR
 BOTH ZONE 4 & ZONE 5, INDICATE THESE ZONES ON THE
 PLANS.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) STOREFRONT PLANS AND CALCULATIONS ARE FOR ZONE 4,
 ALSO SHOW CALCULATIONS AND LOCATION FOR END ZONES (ZONE
 5).
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) 2ND REQUEST, THE DESIGNER OF RECORD REVIEWED THIS
 PRODUCT FOR ZONE 4, WITH THE
 NEW CALCULATIONS FOR ZONE# 5, THE PRESSURES SHALL BE
 GREATER AND REQUIRE ADDITIONAL
 SUPPORTS.
 PLEASE HIGHLIGHT IN THE REPORT WHICH ANCHORING SYSTEM
 TO BE USED, MULLIONS AND GLASS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  