Plan Review Notes
Plan Review Notes For Permit 06100691
Permit Number 06100691
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-16 15:22:01BUILDING PLAN REVIEW
 PERMIT: 06100691
 ADD: 4455 MEDICAL CENTER WAY
 CONT:CORPORATE SIGNS,INC
 TEL: (305)500-9313
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 1ST
 ACTION: DENIED
  
 1)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) FBC. 1609.1 PROVIDE ENGINEERED DRAWINGS WHICH ARE
 DESIGNEDTO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED
 HEREIN. THE ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS. F.A.C. 61G15-23.002.
  
 3) FBC.106.1.1.THE INFORMATION ON THE APPLICATION IS
 NOT CLEAR.CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CALRITY TO INDICATE THE NATURE OF THE WORK.
  
 4)THE APPLICATION SUBMITTED IS PHOTO-COPIED. THIS
 APPLICATION HAS TO BE ORIGINALLY SIGN BY THE CONTRACTOR
 . A NEW APPLICATION REQUIRED WITH ALL ORIGINAL WRITTEN
 INFORMATION.
  
 5) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE, OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 6) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726