| Date |
Text |
| 2006-11-03 19:30:09 | *** UNSAT *** |
| | |
| | 1) NOTE; PLEASE SEE THE VALUATION FOR SCOPE OF WORK |
| | APPLIED FOR SHALL BE BASED ON ALL LABOR AND MATERIALS |
| | EVENS OF OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS |
| | VERY LOW FOR THIS FOUNDATION AND AMOUNT OF |
| | CONCRETE/STEELETC WORK SHOWN. PLEASE SEE BUILDING |
| | REVIEW NOTES. |
| | FBC ADMIN SECT 108.3 |
| | |
| | 2) NOTE:PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS |
| | AS REQUIRED UNDER FLORIDA STATUTES 481.219/471.023 FAC |
| | 61G1-16.004, 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE REVIEW COMMENTS UNDER THE MAIN |
| | BUILDING PERMITS. |
| | PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT |
| | INSTALLATION UNDER SLAB. |
| | 215.5, 230.70, 230.6, 230.70 ETC. |
| | PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS |
| | THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT |
| | LOCATION. |
| | |
| | 4) NOTE: PLEASEALSO SUBMIT GROUNDING ELECTRODE |
| | CONNECTION DETAIL AS REQUIRED PER 250.50. (FOOTER |
| | STEEL, UNDER GROUND COLD WATER PIPES ETC REQUIRED). |
| | THERE ARE NO EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF |
| | 250.50. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |