| Notes |
| Date |
Text |
| 2006-10-18 13:57:44 | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS FOR THE TAMKO MODIFIED SYSTEM | | | REQUIRES RAS 117 CALCULATIONS FROM AN ARCHITECT, | | | ENGINEER OR REGISTERED ROOF CONSULTANT FOR THE REQUIRED | | | ENHANCED FASTENING AT THE PERIMETER AND CORNERS. SEE | | | PAGE 20 OF THE NOA. SUBMIT CALCULATIONS. | | | | | | 2) SPECIFY THE ROOF PITCH AND MEAN ROOF HEIGHT FOR THE | | | SLOPED ROOF. | | | | | | 3) THE ELK SHINGLE NOA DOES NOT ALLOW THEM TO BE | | | INSTALLED ON ROOFS WITH A MEAN HEIGHT OF MORE THAN 33 | | | FEET. SEE LIMITATIONS ON PAGE 2 OF THE NOA. | | | | | | 4) PLEASE INDICATE THE SQUARE FOOTAGE OF FLAT AND | | | SLOPED ROOF SEPARATELY ON THE APPLICATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|