2006-12-13 16:07:28BUILDING PLAN REVIEW
 PERMIT: 06100619
 ADD: 1609 FORUM PL. SUITE# 110
 CONT: PASS INTERNATIONAL
 TEL: (561)702-7201
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE NEW EXIT DOOR "B" IS MISSING THE 18" ON THE
 LATCH SIDE, ALSO SEE LOCATION OF FIRE EXTINGUISHER AND
 PROJECTIONS.
  
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
 11-4.4.4 PROTRUDING OBJECTS.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM
 FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE
 THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND
 FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING
 SPACE [SEE FIGURE 11-8 (E)].
 1003.3.3 HORIZONTAL PROJECTIONS.
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27
 AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR.
 HANDRAILS CAN PROJECT UP TO 4? INCHES (114 MM) FROM THE
 WALL.
  
 2) THE EXISTING DOOR BETWEEN THE RECEPTION ROOM AND
 CORRIDOR IS ALSO MISSING THE 18" LATCH SIDE. UNDER THE
 DISPROPORTIONATE COST THIS DOOR TO BE CORRECTED.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026