| Plan Review Notes For Permit 06100592 |
| Permit Number |
06100592 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-29 13:48:19 | BUILDING PLAN REVIEW | | | PERMIT:06100592 | | | ADD:2139 PBL BLVD | | | CONT:KNIGHT ELECTRIC CO. INC. | | | TEL: (561)689-2876 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW1ST | | | ACTION: DENIED | | | | | | 1) 2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 2) THEEFFECTIVE PROJECTED AREA OF THE LIGHT FIXTURE | | | ON THE POLE IN REFERENCE TO WIND IS REQUIRED. | | | | | | 3) 61G15-23.002 (2)THE DRAWINGS SUBMITTED REQUIRE THE | | | EMBOSSED SEAL OF THE ENGINEER RESPONSIBLE FOR THE | | | DESIGN.IF PRACTICING THROUGH A DULY AUTHORIZE | | | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. | | | NOTE: THE DRAWINGS EVEN STATES THAT THE PLANS ARE NOT | | | VALID WITHOUT THE ENBOSSED SEAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | |
|