2007-02-11 15:21:56** UNSAT ** 2ND REVIEW
  
  
  
 1) NOTE: THIS WAS STATED IN THE PREVIOUS REVIEW AND
 ONLY ONE SET OF REVISED PLANS WAS SUBMITTED? PLEASE
 SUBMIT THREE COMPLETE SETS OF PLANS FOR PROJECT. THIS
 IS A THRESHOLD PROJECT. 106.1.2,106.3.5.5,109.3.6
 PLEASE SEE THERE IS SOME CONFUSION OVER THE SCOPE OF
 WORK APPLIED FOR AND THE PLANS SUBMITTED FOR THE
 PREVIOUS REVIEW AND THE PLANS NOW SUBMITTED FOR THIS
 REVIEW.
 THE PREVIOUS PLANS WERE FOR FOUNTAINS, THE APPLICATION
 WAS FOR FOUNTAINS AND ELECTRICAL REVIEW WAS REQUESTING
 ELECTRICAL INFORMATION FOR THESE. PLEASE SEE THREE OLD
 SHEETS (FROM FIRST REVIEW) WAS SUBMITTED BACK AND NOW
 NEW PLANS (ONLY ONE SET) FOR THE POOL WHICH IS ON THE
 ROOF. PLEASE KNOW WHEN PERMITTING THE POOL ON THE ROOF,
 IT SHOULD BE CAREFULLY TIMED AS THE PERMIT EXPIRES WITH
 IN 6MONTHS WITH NO ACTIVITY.
 ** PLANS SUBMITTED WHICH ARE FROM BASE BUILDING SET ARE
 ALSO FOR THE POOL ON ROOF.
  
 ** NO REVIEW CAN BE DONE AS COMPLETED SETS FOR APPLIED
 SCOPE OF WORK WAS NOT SUBMITTED.
  
 2) NOTE: PLEASE SUBMIT A COMPLETE WIRING DIAGRAM, FOR
 ALL EQUIPMENT, PANEL SCHEDULES AND LOAD CALCULATIONS
 FOR ALL EQUIPMENT.
 PLEASE CLARIFY THE PANEL SHOWN WHERE AND HOW PANEL IS
 FED? EXISTING NEW? ETC.
 PLEASE SEE ALL CONTINUOUS LOADS TO BE FIGURED AND SHOWN
 AT 125%.
 215.3,230.42,680.9 OCP ETC.
 PLEASE SEE 220, 215.5, 240.4,310.16,408.4, ETC ECT.
  
  
 ** PLANS ARE NOT COMPLETE AT THIS TIME AND THERE MAY BE
 FURTHER COMMENTS UPON NEXT SUBMITTIAL OF PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved