| Plan Review Notes For Permit 06100587 |
| Permit Number |
06100587 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-07 07:27:36 | DENIED | | | REFERENCE: FBC-2004 CHAPTER 1 | | | FBC-2004 PLUMBING | | | FLORIDA STATUTES | | | WPB MUNICIPAL CODE | | | | | | 1. MINIMUM 3 SETS OF PLANS REQUIRED FOR THE FOUNTAINS | | | AS THIS IS A THRESHOLD PROJECT. SECTIONS 106.1.2, | | | 106.3.5.5 109.3.6 AND FS 533.71(7). | | | | | | 2. CORRECT APPLICATION TO REFLECT THE DESCRIPTION OF | | | WORK UNDER THE PERMIT. (SHOWS TWO FOUNTAINS). | | | | | | 3. PLANS INDICATE THAT THE OVERFLOW WILL DRAIN TO THE | | | WASTE SYSTEM. OVERFLOW SHALL CONNECT TO THE STORM | | | SYSTEM. SECTION 90-125(5). | | | | | | 4. PLANS INDICATE 3/4" FILL LINE. BACKFLOW PREVENTION | | | IS REQUIRED FOR THE SUPPLY LINE. PLEASE INDICATE | | | METHOD. SECTION 608. | | | | | | 5. DRAIN FROM FILTERS SHALL BE CONNECTED TO THE | | | SANITARY SYSTEM. PLEASE INDICATE ON PLANS. SECTION | | | 301.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|