Plan Review Notes
Plan Review Notes For Permit 06100587
Permit Number 06100587
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-07 07:27:36DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
 FLORIDA STATUTES
 WPB MUNICIPAL CODE
  
 1. MINIMUM 3 SETS OF PLANS REQUIRED FOR THE FOUNTAINS
 AS THIS IS A THRESHOLD PROJECT. SECTIONS 106.1.2,
 106.3.5.5 109.3.6 AND FS 533.71(7).
  
 2. CORRECT APPLICATION TO REFLECT THE DESCRIPTION OF
 WORK UNDER THE PERMIT. (SHOWS TWO FOUNTAINS).
  
 3. PLANS INDICATE THAT THE OVERFLOW WILL DRAIN TO THE
 WASTE SYSTEM. OVERFLOW SHALL CONNECT TO THE STORM
 SYSTEM. SECTION 90-125(5).
  
 4. PLANS INDICATE 3/4" FILL LINE. BACKFLOW PREVENTION
 IS REQUIRED FOR THE SUPPLY LINE. PLEASE INDICATE
 METHOD. SECTION 608.
  
 5. DRAIN FROM FILTERS SHALL BE CONNECTED TO THE
 SANITARY SYSTEM. PLEASE INDICATE ON PLANS. SECTION
 301.3.
  