| 2007-12-19 16:46:00 | REVIEW #: 12B |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | REV 11 COMMENTS: |
| | |
| | 2. M1-1.1WRITTEN RESPONSE INDICATES A FIRE DAMPER IS |
| | NOT REQUIRED IN THE 6X6 TRANSFER DUCT AT THE FIRE |
| | COMMAND CENTER (ROOM A1.120) BECAUSE THE SECTION OF |
| | WALL WHERE THE TRANSFER DUCT IS LOCATED IS NOT SHOWN TO |
| | BE FIRE RESISTANCE RATED ON THE LIFE SAFETY PLAN. |
| | WHETHER OR NOT IT IS SHOWN AS RATED, THE FIRE COMMAND |
| | CENTER IS REQUIRED TO BE SEPARATED FROM THE REMAINDER |
| | OF THE BUILDING BY NOT LESS THAN A 1-HOUR FIRE |
| | RESISTANCE RATED FIRE BARRIER IN ACCORDANCE WITH FBC |
| | 911.1. AS SUCH THIS WALL IS REQUIRED TO BE RATED. |
| | THEREFORE A FIRE DAMPER IS REQUIRED PER FBC, M 607.5. |
| | |
| | 5. OK |
| | |
| | 6. M1-2.1: PLEASE INCLUDE KEY NOTE #6 AT THE FIRE/SMOKE |
| | DAMPERS WHERE THE SMOKE EXHAUST DUCTS PENETRATE THE |
| | SHAFT ENCLOSURE. THEY ARE REQUIRED FOR THE OPERATION OF |
| | THE SMOKE CONTROL SYSTEM. THEREFORE THEY SHOULD BE |
| | CONTROLLED IN ACCORDANCE WITH FBC, M 513.5.2. |
| | |
| | 13. OK |
| | |
| | 14. OK |
| | |
| | REV 10 COMMENTS: |
| | |
| | 3. OK |
| | |
| | 5. OK |
| | |
| | REV 12A COMMENTS: |
| | |
| | 1. M4-4.0: SMOKE CONTROL SEQUENCE NOTE #4, SMOKE |
| | CONTROL SYSTEM SHALL ACTIVATE FROM ATRIUM SMOKE |
| | DETECTORS OR DETECTION OF FLOW IN THE FIRST OR SECOND |
| | FLOOR FIRE SPRINKLER PIPING SERVING THE ATRIUM. |
| | |
| | 2. OK |
| | |
| | 3. A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE |
| | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF |
| | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS |
| | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE |
| | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT |
| | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS |
| | 909.4.1 THROUGH 909.4.6 IN ACCORDANCE WITH FBC 909.4. |
| | |