| 2007-09-09 12:56:26 | 2007-09-09 12:56:26 |
| | REVIEW COMPLETED, NOTES BELOW. |
| | |
| | ** DENIED REVISIONS ** |
| | |
| | 1) NOTE: PLEASE SEE SHEET E0-2.2 WHICH INDICATES |
| | CONDUITS FOR LIGHTING IN THE RIGHT OF WAY ON THE PLANS |
| | FOR THIS BUILDING. THIS IS TO BE INCLUDED ON SEPARATE |
| | PLANS AND UNDER SEPARATE PERMITS WHICH IS NOT A PART OF |
| | THIS BUILDING OR LEGAL PROPERTY. |
| | |
| | 2) NOTE: PLEASE SEE *PROVISO* AND *DENIAL* COMMENTS |
| | FROM JULY 27TH, 2007 WHICH HAVE NOT BEEN ADDRESSED. AS |
| | SOME OF THE REVISED SHEETS SUBMITTED DO HAVE A FEW OF |
| | THESE ITEMS DONE, MOST HAVE NOT. |
| | PLEASE SEE THE ATTACHED NOTES FOR THAT DATE. |
| | THESE NEED TO BE ADDRESSED AND INCORPORATED INTO PLAN |
| | SETS AS SOON AS POSSIBLE TO ALLEVIATE CONFUSION AND |
| | REVISIONS BEING MIXED AND/OR MISSED ALONG THE WAY. FBC |
| | ADMIN SECTION. 106.1.2,106.3.1 ETC |
| | |
| | 3) NOTE: PLEASE SEE NUMEROUS SHEETS HAVE BEEN REVISED |
| | WITH CIRCUITING, LOADS INCREASING, ADDED POWER |
| | LOCATIONS, ADDED RECEPTACLES ETC HOWEVER NOT REVISED |
| | PANEL SCHEDULES OR LOAD CALCULATIONS WERE SUBMITTED. |
| | PLEASE SEE THE PANEL SCHEDULES AND LOADS ON FILE DO NOT |
| | CONTAIN MANY OF THE NEW CIRCUITS NOW SHOWN. |
| | PLEASE SEE THE PANEL SCHEDULES DO NOT CONTAIN THE |
| | INCREASE IN LOADS BY THE ADDED DEVICES ETC. |
| | PLEASE COORDINATE AND REVISE LOAD CALCULATIONS FOR |
| | AFFECTED PANELS. PLEASE REVISE PANEL SCHEDULES |
| | ACCORDINGLY. |
| | PLEASE SEE SHEET E1-5.1 ROOM A5.406 AS SOME RECEPTACLES |
| | WERE REVISED AND DO NOT CONTAIN CIRCUITING. |
| | PLEASE SEE THIS SAME SHEET AS RECEPTACLES ADDED TO |
| | CIRCUIT(S) 5LA3-5, 5LA3-34 DO NOT CORRELATE WITH LOADS |
| | AND PANEL SCHEDULES. THIS IS TYPICAL OF NUMEROUS |
| | CIRCUITS, LOADS, SHEETS AND PANELS. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 408.4, 220 ETC |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS ON |
| | SHEETS WHERE THE FURNITURE LAYOUTS HAVE NOW BEEN |
| | REMOVED. ?? |
| | |
| | 5) NOTE: AS NOTED AND AGREED BY THE CONTRACTOR, OWNER |
| | AND AS SHOWN ON ORIGINAL PLANS, THE LOW VOLTAGE SYSTEMS |
| | ARE TO BE UNDER A SEPARATE PERMIT AND ARE NOT PART OF |
| | THE BASE BUILDING PLANS AND PERMITTING. |
| | PLEASE SUBMIT THREE COMPLETE SETS WITH PERMIT |
| | APPLICATION, APPROPRIATE VALUE AND FEES FOR THE SCOPE |
| | OF WORK. |
| | ** PLEASE BE SURE TO SPECIFY THE TYPE OF CABLING, |
| | CONDUIT INSTALLATION ETC. |
| | |
| | 6) NOTE: PLEASE EXPLAIN TITLE BLOCKS WITH |
| | IDENTIFICATION OF REVISIONS. THE SHEETS ARE LABELED AS |
| | REV # 11, YET THE DESCRIPTION INDICATES THIS IS |
| | REVISION #3? |
| | THIS IS UNCLEAR. |
| | ALTHOUGH NOT REQUIRED, PLEASE KNOW A SUBMITTAL OF A |
| | LETTER ON REVISIONS TAKING PLACE ALONG THE PROCESS OF |
| | THE JOB WOULD HELP TO PERHAPS ALLEVIATE ANY CONFUSION |
| | AND DELAYS IN PROJECT. |
| | |
| | ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-08 21:29:06 | 2007-09-08 21:29:06 |
| | |
| | REVIEW COMMENCED. |
| 2007-09-05 19:19:08 | 2007-09-05 19:19:08 |
| | 1-ROLL IN ELECTRICAL FOR REVIEW: |