| 2007-08-01 13:22:22 | 1. THE CARBON MONOXIDE SENSORS DISPLAYED ON THE |
| | MEHANICAL SHEETS ARE TO BE INSTALLED PER MANUFACTURER'S |
| | REQUIREMENTS. WHAT SET POINTS ARE THE CARBON MONOXIDE |
| | DETECTORS GOING TO BE SET AT. THESE DEVICES WILL NEED |
| | TO BE TESTED WITH CALIBRATION GAS AFTER INSTALLATION. |
| | PLEASE PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR |
| | THESE DEVICES. PLEASE PROVIDE DETAILS ON CARBON |
| | MONOXIDE SYSTEM. THE INSTALLATION LOCATIONS FOR THESE |
| | DEVICES SHALL NOT EXCEED MAXIMUM COVERAGE AREAS OR |
| | SPACING REQURIEMENTS. |
| | |
| | 2. ALL ELECTRICAL REVISIONS TO COMPLY WITH NFPA 70, THE |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 3. THE INSTALLATION OF THE CHAIN LINK FENCE FOR THE |
| | FUTURE GENERATOR AND ANY PARKING SPACES SHALL NOT |
| | INTERFERE WITH ANY EXIT ACCESS TO STAIR # 4. |
| | |
| | 4. THE OPERATION OF EMERGENCY LIGHTING EQUIPMENT EVEN |
| | IF THEY ARE EQUIPPED WITH OCCUPANCY SENSORS SHALL |
| | COMPLY WITH THE OPERATIONAL REQUIREMENTS OF CHAPTER |
| | SEVEN OF THE LIFE SAFETY CODE. |
| | |
| | 5. NO EMERGENCY PHOTOMETRICS DISPLAYED IN FIRE COMMAND |
| | CENTER ON PAGE E-8-1.1. |
| | |
| | 6. PLEASE BE ADVISED THAT LARGE BATHROOMS MUST BE |
| | EQUIPPED WITH EMERGENCY LIGHTING. LARGE RESTROOMS CAN |
| | BE EXTREMELY DARK WHEREBY ACCESS TO THE INGRESS/EGRESS |
| | DOOR FROM THE ROOM CAN BE IMPOSSIBLE. |
| | |
| | |