| 2007-09-10 17:14:48 | REVISIONS DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT P1-1.0 CLOUD AND NUMBER ALL REVISIONS. REVISIONS |
| | SEEN WITH NO CLOUDS OR REVISION NUMBERS. SECTION |
| | 106.1.3. |
| | |
| | 2. SHTS P1-2.0 & P1-2.1 ROOM A2.316 SINK SHALL BE |
| | ACCESSIBLE. PLEASE SHOW CLEAR FLOOR SPACE AND TURNING |
| | AREA REQUIRED BY SECTIONS 11-4.24.5 & 11-4.2.3.-- |
| | CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3. |
| | |
| | 3. SHT P3-20 RISERS DO NOT REFLECT THE FLOOR PLAN.-- |
| | RISER P/2, SEE PROVISO FOR CLEANOUT DOWNSTREAM OF |
| | JANITOR SINK 3RD FLOOR. SEE PREVIOUS APPROVED SHEETS |
| | WITH COMMENT ABOUT REVISIONS.--SINK S-1 BY THE BASE |
| | OF RISER P/4, (RM A1.709), DOES NOT REFLECT REVISION |
| | #11 CHANGE.--SINK S-1 BY THE TOILET ROOM A2.705 |
| | CONNECTS TO BOTH RISERS P/7 & P/4. PLEASE CLARIFY.-- |
| | SINK SK-1 DOWNSTREAM OF TOILET ROOM A2.107 DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH |
| | THE FLOOR PLANS. SECTION 106.1.1. |
| | |
| | 4. SHT P3-3.0 RISER DOES NOT REFLECT THE FLOOR PLAN FOR |
| | THE OFFSET OF THE SINK IN THE JANITOR ROOM, NOR FOR THE |
| | CLEANOUT PRIOR TO THE SINK UPSTREAM OF THE EWC-1 BY THE |
| | JANITOR ROOM A4.105. PLEASE CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 106.1.1. |
| | |
| | 5. SHT P3-6.0 THE WATER LINES FOR THE SINK BY THE |
| | ELECTRIC W/H IN THE JANITOR ROOM A4.105 DO NOT REFLECT |
| | THE SINK LOCATION ON THE FLOOR PLAN. THE RISER SHOWS |
| | THEM TURNING INTO THE JANITOR ROOM, BUT THE FLOOR PLAN |
| | SHOWS THE SINK IN THE HALLWAY OUTSIDE THE JANITOR ROOM. |
| | THE WATER RISER FOR THE TOILET ROOM A2.105 DOES NOT |
| | REFLECT THE PIPING SHOWN ON SHT P2.30 FOR THE SINK IN |
| | ROOM A2.730. PLEASE CORRELATE RISER AND FLOOR PLANS. |
| | SECTION 106.1.1. |
| | |