| Date |
Text |
| 2007-04-14 11:48:58 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THIS REVIEW IS FOR REVISION #8 AS |
| | SUBMITTED TO ADDRESS *PROVISO* FROM ISSUANCE OF |
| | PERMIT** |
| | |
| | ** PLEASE SEE THAT MOST OF THE *PROVISO* NOTES HAVE |
| | BEEN ADDRESSED HOWEVER DUE TO CHANGES IN REVISION #7 |
| | AND SOME ITEMS WHICH STILL NEED TO BE REVISITED ON |
| | PROVISO, PLEASE SEE THE COMMENTS BELOW. |
| | |
| | 1) NOTE: PLEASE KNOW THAT DUE TO THE CLEARANCE |
| | REQUIREMENTS FOR THE GENERATOR WHICH WAS COMMENTED ON |
| | IN REVISION FOR ARCHITECTURAL DATED 3/1/07 THE PLANS AS |
| | SUBMITTED DO NOT INDICATE THE MINIMUM CLEARANCES FOR |
| | THE UNIT PER NEC 110.26 AND THAT WHICH IS SET-FORTH |
| | FROM THE MANUFACTURES SPECIFICATIONS. |
| | 110.3, 90.7 |
| | |
| | 2) NOTE: PLEASE CLARIFY THE CONTROL DEVICE FOR ELEVATOR |
| | ROOM PER 1-6.1. OCCUPANCY DEVICE REQUIRED. |
| | 13-415.1.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE SEE PANEL 1-HEE WHICH NEEDS TO INDICATE |
| | AND LABEL THE ROOMS IN WHICH THEY FEED AND THE |
| | DESIGNATION FOR THE * ELEVATOR MACHINE RM LTS*. |
| | 408.4, 620.23 |
| | |
| | 4) NOTE: PLEASE SEE THE PROVISO WHICH WAS TO REVISE |
| | CIRCUITS FOR THE ELEVATOR ROOMS, WHICH WAS TO INCLUDE |
| | THE LIGHTING AND RECEPTACLES, YET ONLY THE REVISED |
| | LIGHTING PLANS WERE SUBMITTED. PLEASE SEE THE SHEETS |
| | FOR THESE ROOMS SHOULD HAVE ALSO BEEN SUBMITTED. |
| | 620.23 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AND |
| | NOTES FOR REVISION #7 WHICH AHS NOT BEEN CHANGED. |
| | PLEASE SEE THAT THE ATS SWITCHES WHICH HAVE BEEN |
| | REVISED ON OTHER DOCUMENTS HAVE NOT BEEN REVISED ON |
| | RISER DIAGRAM. |
| | PLEASE SEE NOTES DATED 3/24/07 |
| | PLEASE BE SURE TO REVISE POWER PLANS, PANEL SCHEDULES, |
| | LOADS ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE CLARIFY STAIR 11 LIGHTS AND LOCATIONS |
| | FOR THE PHOTO-METRIC LEVELS. PREVIOUS PLANS INDICATE |
| | LIGHTING IN THE STAIR AREA ABOVE THE STAIRS AND SOME |
| | SHEETS INDICATE THESE AT THE UPPER LEVEL AND LOWER |
| | LEVEL WHICH DO NOT SEEM THEY WOULD PROVIDE THE NEEDED. |
| | PLEASE SEE THE PHOTO-METRIC PLANS WHICH DO INDICATE THE |
| | LIGHT FIXTURE ABOVE STAIRS AND IF THIS IS HOW THE |
| | LIGHTING LEVELS ARE DERIVED THEN THE PLACEMENT OF THE |
| | LIGHTING FIXTURES ON THE LIGHTING PLANS WOULD NOT WORK |
| | AND PROVIDE THE LIGHTING. |
| | LS 101 7.8.1.3, 7.9.2.2 |
| | PLEASE SEE NEXT COMMENT. |
| | |
| | 7) NOTE: PLEASE SEE THAT LIGHTING PLANS AND |
| | PHOTO-METRIC PLANS STILL NEED COORDINATION OG LIGHTING |
| | FIXTURES. PLEASE SEE THAT THE SAME FIXTURES WHICH ARE |
| | INDICATED AS EM TYPE FIXTURES ON LIGHTING PLANS ARE NOT |
| | THE SAME ONES IN ALL LOCATIONS ON PHOTO-METRIC PLANS. |
| | PLEASE KNOW AS BASED ON COMMENT ABOVE AND THE NEXT |
| | COMMENT FOR NIGHT LIGHTING AND EMERGENCY LIGHTING, |
| | THESE WILL ALL NEED TO BE ADJUSTED AND REVISED TO |
| | CORRELATE. |
| | FBC 106.1.2 |
| | LS 101 7.8, 7.9 |
| | |
| | 8) NOTE: PLEASE KNOW THAT A MEETING WILL BE REQUIRED TO |
| | GO OVER PLANS AND PROPOSED *NIGHT-LIGHTS* AS SHOWN ON |
| | PLANS. PLEASE KNOW THAT EMERGENCY FIXTURES ARE REQUIRED |
| | FOR EGRESS PATHS UNDER NORMAL AND EMERGENCY HOWEVER THE |
| | NUMBER OF FIXTURES BEING PROPOSED FOR NIGHT LIGHTS |
| | WHICH WILL BE LEFT *ON* 24/7/365 DOES NOT TAKE INTO |
| | CONSIDERATION OF THE REQUIREMENT OF THE FLORIDA ENERGY |
| | CODE. |
| | PLEASE SEE THESECTION BELOW WHICH IS TAKEN DIRECTLY |
| | FROM NFPA-101. *7.8.1.2.2* WHICH IS LOCATED ALONG WITH |
| | TEXT FOR SECTION OF 7.8. |
| | PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE EGRESS |
| | LIGHTING, THE ACTUAL DESIGNATED EGRESS PATH/PATHS NEEDS |
| | TO BE DETERMINED AS A STARTING POINT FOR FINDING THE |
| | MINIMUM REQUIRED. |
| | PLEASE KNOW THAT THIS OFFICE HAS CONTACTED THE FLORIDA |
| | BUILDING COMMISSION TO GO OVER THE REQUIREMENTS OF |
| | CHAPTER 13 AND THE INTENT.CONSIDERATION NEEDS TO BE |
| | GIVEN FOR THE INTENT AND AT THE SAME TIME MEETING THE |
| | REQUIRED LIFER SAFETY FOR NORMAL AND EMERGENCY EGRESS |
| | LIGHTING DURING OCCUPANCY OF BUILDING. |
| | |
| | *7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11 |
| | THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND |
| | PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| | THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A |
| | PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| | 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH |
| | LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY |
| | TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA |
| | VALUES HEREIN SPECIFIED. |
| | 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING |
| | SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, |
| | PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR |
| | FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET |
| | FOR MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR |
| | IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA |
| | SERVED BY THE LIGHTING UNITS. |
| | |
| | ** PLEASE SEE ONE SET OF THE PLANS WHICH WAS SUBMITTED |
| | HAS REDLINED LOCATIONS WHICH ARE ALSO HIGH-LIGHTED FOR |
| | AREAS WHICH NEED TO BE GONE OVER. |
| | ** PLEASE CONTACT THIS OFFICE ONCE THE MINIMUM |
| | LIFE-SAFETY DESIGNATED EGRESS PATHS ARE DONE TO SET UP |
| | A MEETING TO GO OVER PLANS AND SCENARIOS. |
| | |
| | ** PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE NOTES |
| | ABOVE AND THE TIME CONSIDERATION WHICH WILL BE GIVEN TO |
| | ADDRESS THE ABOVE, THE ORIGINAL DATE OF 60DAYS HAS BEEN |
| | EXTENDED AS DISCUSSED WITH THE ENGINEER OF RECORD. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-14 09:59:47 | REVIEW IN PROGRESS |