| 2009-06-10 11:26:23 | ** DENIED REVIEW** |
| | |
| | ** PLANS AND FINAL REVISIONS NEED TO BE SUBMITTED WITH |
| | COORDINATION OF ALL DRAWINGS. THESE ARE THE FINAL |
| | RECORD PLANS TO BE ON FILE. ALL ITEMS NEED TO BE |
| | COORDINATED AND CORRECTED. |
| | |
| | * THE FOLLOWING WILL BE SOME EXAMPLES ONLY OF AREAS IN |
| | WHICH THERE ARE DISCREPANCIES ON PLANS. |
| | |
| | **** THIS REVIEW IS NOT BASED ON THE COMPARISON OF |
| | PLANS WITH THE FIELD OR JOBSITE LOCATION. |
| | |
| | **** ONE OF THE REDLINED SET OF PLANS WHICH WAS USED IN |
| | REVIEW WILL REMAIN IN THIS OFFICE. IN NUMEROUS PREVIOUS |
| | REVIEWS AND MEETINGS IT WAS STATED TO CALL TO GO OVER |
| | ANY QUESTIONS ON COMMENTS WITH RESPECT TO PLANS OR |
| | PROPOSED DESIGN. IT IS STRONGLY RECOMMENDED THAT A |
| | MEETING BE HELD TO GO OVER ANY COMMENTS WHICH MAY NOT |
| | BE CLEAR OR UNDERSTOOD IN ANY WAY. THIS MEETING SHOULD |
| | BE HELD WITH REPRESENTATIVES FROM THE GENERAL |
| | CONTRACTOR, ELECTRICAL CONTRACTOR, ARCHITECTURAL FIRM, |
| | ENGINEERING FIRM AND THE CITY OF WEST PALM BEACH. |
| | |
| | **** THE LIGHTING CONTROL PANEL WILL BE NOTED AS LCP IN |
| | MANY OF THE COMMENTS BELOW. |
| | |
| | **** MANY OF THE COMMENTS BELOW WILL BE GENERAL TO THE |
| | SECTIONS OF CODES FOR LIGHTING CONTROLS, PANEL SCHEDULE |
| | AND RECORD PLANS. |
| | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. 408.4, 106.5, |
| | 106.1.1, 106.1.2 ETC |
| | MORE SPECIFIC CODES WILL BE NOTED IN OTHER LOCATIONS. |
| | ** PLEASE BE SURE TO SEE 408.4 WHICH REQUIRE ALL |
| | LOCATIONS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. STATING *RECEPTACLES* OR * LIGHTING* IS NOT |
| | SPECIFIC FOR PANEL SCHEDULES OR PANEL SCHEDULES ON |
| | RECORD PLANS. |
| | |
| | 1) NOTE: PLEASE SUBMIT AN UPDATE LAYOUT OF ALL |
| | ELECTRICAL ROOMS WHICH EQUIPMENT WAS ADDED. FOR EXAMPLE |
| | THERE ARE NEW TRANSFORMERS AND PANELS FOR SOME |
| | LOCATIONS THROUGH OUT THE PLANS. THE TRANSFORMER FOR |
| | PANEL A FOR EXAMPLE COULD NOT BE LOCATED ON PLAN. |
| | SEE OTHER NOTES BELOW WITH RESPECT TO OTHER PANELS AND |
| | COORDINATION OF PLANS.110.26, FBC 106.1.2,106.1.1, |
| | 106.5 FOR COORDINATION OF RECORD DOCUMENTS. |
| | THE MAIN ELECTRICAL ROOM IS ONE EXAMPLE OF EQUIPMENT |
| | BEING ADDED WHICH IS NOT PART OF THE REVISED PLANS. THE |
| | RECORD PLANS DO NOT INCLUDE OTHER WORK WHICH HAS BEEN |
| | DONE. |
| | |
| | 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW PANEL *A* |
| | WHICH IS NOW SHOWN ON PLANS. PLEASE BE SURE TO |
| | COORDINATE. 408.4 |
| | |
| | 3) NOTE: PLEASE SHOW LOCATION OF THE TRANSFORMER FOR |
| | THE SAME PANEL *A*. 450.9, 450.13, 110.26 ETC. AS THIS |
| | IS NOT SHOWN CODE COMPLIANCE CAN NOT BE DETERMINED. |
| | |
| | 4) NOTE: PLEASE REMOVE ALL WORK IN AREAS FOR WHICH THE |
| | *PHOTO MUSEUM* WILL BE LOCATED. ONE EXAMPLE IS THE 2ND |
| | FLOOR WHICH STILL INDICATES LIGHTING AND OTHER ITEMS |
| | WHICH ARE NOW NO LONGER PART OF THE BASE BUILDING. |
| | PLEASE TAKE A LOOK AT THEIR TENANT SPACE PLANS AND |
| | REMOVE LIGHTS AS NEEDED. |
| | PLEASE ALSO COMPLETE LATEST REVISED PLANS FOR COMMON |
| | AREAS WHICH ARE TO BE FED FROM BASE BUILDING AND ARE |
| | NOT PART OF THE TENANT SPACE. |
| | THE RISER STILL INDICATES THE 800A BREAKER FOR THE |
| | PHOTO-MUSEUM EVEN THOUGH THE SPACE IS FED FROM A |
| | SEPARATE SERVICE. |
| | SEE D2.106 |
| | |
| | 5) NOTE: RECEPTACLES IN MAIN MECHANICAL ROOM DO NOT |
| | CONNECT TO ANY CIRCUIT. |
| | |
| | 6) NOTE: PLEASE SEE 2-HA-18 WHICH IS SHOWN AS EXTERIOR |
| | LIGHTS ON PLANS YET THE LCP IS NOT COMPLETE OR LISTS |
| | THE CIRCUIT. THE PANEL SCHEDULE FOR HA-18 IS SHOWN AS |
| | SPARE EVEN THOUGH IT IS ON PLANS. |
| | |
| | 7) NOTE: PLEASE SEE 2-HC-18 IS NOTED ON PLANS YET NOT |
| | ON LCP. |
| | |
| | 8) NOTE: PLEASE SEE 2-HA-10 WHICH IS NOT ON LCP. |
| | |
| | 9) NOTE: PLEASE SEE 2-HB-8 WHICH IS SHOWN AS EXTERIOR |
| | LIGHTS ON PANEL SCHEDULE HOWEVER THE LCP STATES THIS IS |
| | FOR LIGHTING INSIDE IN OPEN WORK AREA. |
| | |
| | 10) NOTE: PLEASE SEE 2-HA-19 WHICH IS NOT LISTED ON LCP |
| | HOWEVER ON PLANS AND PANEL SCHEDULE. |
| | |
| | 11) NOTE: PLEASE SEE FIRST LEVEL COMMON AREAS WHICH DO |
| | NOT INDICATE ANY LIGHTING, LIGHTING CONTROLS, AND |
| | CIRCUITS ETC WHICH ARE NOT PART OF THE PHOTO MUSEUM |
| | SPACE. |
| | 13-415.1.ABC.1.1,1.2, .1.3. |
| | |
| | 12) NOTE: PLEASE COMPLETE PLANS WITH NEW LIGHTING FOR |
| | COMMON AREAS OUTSIDE PHOTO MUSEUM SPACE. PLEASE SEE |
| | NFPA-101 7.8 AND 7.9 FOR COMPLETE LIGHTING IN COMMON |
| | AREAS FOR LIFE SAFETY. OTHER ITEMS SUCH AS HORNS, |
| | STROBES, HORN/STROBE FOR COMPLIANCE WITH NFPA-72 AND |
| | COMPLIANCE WITH FBC 11-4.27.4 SHALL ALSO BE MET. FIRE |
| | ALARM PLANS HAVE NOT BEEN UPDATED AND COORDINATED TO |
| | DATE OF THIS REVIEW. |
| | |
| | 13) NOTE: PLEASE SEE EE FIXTURE ON C2-2.2 WHICH DOES |
| | NOT INDICATE ANY CIRCUIT OR CONTROL. THE PREVIOUS PLANS |
| | DID SHOW CIRCUITING AND CONTROLS. |
| | |
| | 14) NOTE: WHERE ARE THE CONTROLS FOR 1-GHA18-20? |
| | |
| | 15) NOTE: PLANS SHOW CIRCUIT 1-GLA-30 AS A DEDICATED |
| | CIRCUIT FOR SODA MACHINE HOWEVER BASED ON THE PLANS |
| | THIS SAME CIRCUIT IS SHOWN IN MORE THAN ONE LOCATION. |
| | ONE LOCATION IS THE STORAGE ROOM IN GARAGE WHICH |
| | INDICATES THE SAME CIRCUIT. |
| | |
| | 16) NOTE: PLEASE SEE CIRCUIT 1LB3-21 AND 24 WHICH BOTH |
| | INDICATE CIRCUITS TO COMMON AREA RECEPTACLES IN SPACE |
| | A1.115. ARE NOT ONE OF THESE AT LEAST A DEDICATED |
| | CIRCUIT FOR SODA MACHINE? |
| | |
| | 17) NOTE: PLEASE SEE CIRCUIT 1-GLEA-2 WHICH INDICATES |
| | PLANS A J-BOX YET THIS IS CIRCUITED AS A FA NAC. |
| | |
| | 18) NOTE: PLEASE SEE 1-LC2-31 ON PLANS SHOWN AS CIRCUIT |
| | TO ROOM C1.101 HOWEVER PANEL SCHEDULE INDICATES |
| | C1.301?? |
| | |
| | 19) NOTE: PLEASE SEE POWER PLANS FOR EXAMPLE E1-1.1 |
| | WHICH DOES NOT SHOW THE NEW PANELS 1TV AND 1LS-1. THESE |
| | ARE SHOWN ON E7-7.0 YET NOT COORDINATED. |
| | THE PANEL SCHEDULE FOR EACH OF THESE INDICATED ROOM |
| | LOCATIONS HOWEVER PANEL NOT AS ON PLANS. ONE OF THESE |
| | WOULD BE 1TV WHICH STATES THE LOCATION AS A1.406 YET |
| | SHEET E7-7.0 SHOWS THIS IN ANOTHER LOCATION NEXT TO |
| | 1LS-1. |
| | |
| | 20) NOTE: PLEASE SEE 1TV WHICH IS SHOWN AS 200AMP MLO |
| | ON SCHEDULE AND ON RISER THIS IS SHOWN AS 150AMP. ?? |
| | |
| | 21) NOTE: PLEASE SEE 1LD2-13 ON PANEL SCHEDULE WHICH |
| | STATES THIS IS FOR AHU-1 PUMP. YET PLANS INDICATE THIS |
| | FOR GENERAL RECEPTACLE CIRCUIT FEEDING OTHER AREAS |
| | BESIDES PUMP? |
| | |
| | 22) NOTE: PLEASE SEE 2-LA-3-3 ON PANEL WHICH STATES |
| | THIS FEEDING LOCATION A2.213 YET THE PLANS SHOWS THE |
| | LOCATION IN FOYER SINGLE LOCATION A2.003. |
| | |
| | 23) NOTE: PLEASE SEE 2LD-2-3 WHICH IS NOT SPECIFIC TO |
| | ROOMS AND LOCATIONS IN WHICH THIS CIRCUIT FEEDS. PANEL |
| | SCHEDULE DOES NOT LIST LOCATIONS AS FOUND ON PLANS. |
| | |
| | 24) NOTE: PLEASE SEE 2LD2-6 WHICH IS SHOWN AS SPARE ON |
| | PANEL SCHEDULE HOWEVER THE PLANS ON E1-2.2 STILL HAS |
| | CIRCUIT SHOWN. |
| | |
| | 25) NOTE: PLEASE CORRELATE ALL POWER AND RELEVANT |
| | CHANGES ON POWER PLANS E1-1.1 WITH E7-7.0. |
| | THERE ARE NUMEROUS ITEMS |
| | |
| | 26) NOTE: PLEASE SEE 1LA3-10 WHICH PER PANEL SCHEDULE |
| | IT STATES COMMISSION OFFICE HOWEVER PLEASE SEE SHEET |
| | E7-7.0 WHICH INDICATES THIS AS A DEDICATE RECEPTACLE IN |
| | THE FLAGLER GALLERY. |
| | |
| | 27) NOTE: PLEASE SEE 1LA3-18 WHICH DOES LIST THIS AS |
| | A1-308 ON PLANS HOWEVER PLEASE SEE E7-7.0 |
| | |
| | 28) NOTE: PLEASE SEE 3LD2-9 NEEDS TO BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. THE PLANS INDICATE |
| | MANY MORE LOCATIONS THAN WHAT IS LISTED ON PANEL |
| | SCHEDULE. |
| | |
| | 29) NOTE: PLEASE SEE 3LC-19 NEED TO BE SPECIFIC TO ALL |
| | ROOMS AND AREAS IN WHICH THEY FEED. |
| | |
| | 30) NOTE: PLEASE SEE 3LD3-21 ON PANEL SCHEDULE WHICH |
| | INDICATES THIS AS A SPARE CIRCUIT HOWEVER THE PLANS |
| | STILL SHOW THIS CIRCUIT. |
| | |
| | 31) NOTE: PLEASE SEE 3LD3-6 WHICH THE PANEL SCHEDULE |
| | INDICATES THIS AS A SPARE YET THE PLANS STILL INDICATES |
| | THIS AS A CIRCUIT BEING USED. |
| | |
| | 32) NOTE: PLEASE SEE CIRCUITS 4LA3-5 AND -24 WHICH ARE |
| | BOTH SHOWN TIED TOGETHER ON PLANS. WHY ARE THESE NOT |
| | SEPARATED? |
| | |
| | 33) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| | STATIONS WHICH SHOW THE SAME CIRCUITING 4LB3-26,28,30. |
| | PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE |
| | INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS |
| | AS SHOWN FOR KNOWN LOADS. THIS WAS GONE OVER IN |
| | ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR KNOWN |
| | LOADS AND LOADS FIGURED AT 180VA. THE REVIEW COMMENTS |
| | CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH QUESTIONS |
| | WERE RAISED. |
| | |
| | 34) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| | STATIONS WHICH SHOW THE SAME CIRCUITING 4LA3-15,17,19. |
| | PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE |
| | INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS |
| | AS SHOWN FOR KNOWN LOADS. |
| | THIS WAS GONE OVER IN ORIGINAL REVIEW EVEN BEFORE |
| | PERMIT ISSUANCE FOR KNOWN LOADS AND LOADS FIGURED AT |
| | 180VA. THE REVIEW COMMENTS CAN BE PROVIDED ALONG WITH |
| | E-MAILS IN WHICH QUESTIONS WERE RAISED. |
| | |
| | 35) NOTE: PLANS STILL STATE IT EQUIPMENT TO BE DONE BY |
| | OTHERS. HOWEVER THE RECORD SET OF PLANS NEED TO NOW |
| | SHOW ALL OF THIS WORK BEING COMPLETED. PLEASE COMPLETE |
| | THE IT PANEL SCHEDULE. THE SCHEDULE DOES INDICATE THE |
| | CIRCUITING FOR AC EQUIPMENT ETC HOWEVER NO OTHER |
| | EQUIPMENT IS SHOWN BEING FED FROM THIS PANEL. |
| | WHERE IS ALL OF THE OTHER EQUIPMENT BEING FED FROM? |
| | CIRCUITS? LOADS? ETC |
| | 408.4,310.16,240.3,220, ETC |
| | 645 (ALL) |
| | |
| | 36) NOTE: PLEASE PROVIDE INFORMATION ON THE EPO AT THE |
| | DOOR FOR IT ROOM. |
| | PLEASE SEE 645.10 FOR THE REQUIRED DISCONNECTING MEANS |
| | TO ALL EQUIPMENT INCLUDING AC EQUIPMENT. |
| | THERE IS A CIRCUIT ON 1LED-27 FOR SHUNT TRIP CIRCUIT |
| | HOWEVER THE IT PANEL OR FEED TO IT PANEL DOES NOT |
| | INDICATE ANY SHUNT TRIP TYPE MAIN BREAKER OR BRANCH |
| | BREAKER. THE RISER DOES NOT INDICATE A SHUNT FOR ANY OF |
| | THE MAIN BREAKERS OR FEEDERS. |
| | PLEASE PROVIDE INFORMATION AND DETAIL FOR THIS. |
| | |
| | 37) NOTE: PLEASE SEE 4LEB-10 WHICH IS SHOWN AS SPARE ON |
| | PANEL SCHEDULE YET THE PLANS STILL INDICATE THIS |
| | CIRCUIT. |
| | |
| | 38) NOTE: PLEASE SEE 4IT 15,17 ON PANEL SCHEDULE THIS |
| | IS SHOWN TO RM A4.416 YET THE PLANS DO NOT INDICATE |
| | THIS. |
| | |
| | 39) NOTE: PLEASE SEE 4LD2- 5 STATES RECEPTACLES IN ROOM |
| | 4-106 HOWEVER THIS IS SHOWN ON PLANS FEEDING OTHER |
| | AREAS ALSO. |
| | |
| | 40) NOTE: PLEASE SEE 4LC2-13 WHICH IS SHOWN ON PANEL TO |
| | ROOM A4-201 HOWEVER ON PLANS THIS IS LOCATED AT THE |
| | OTHER END OF THE FLOOR. |
| | |
| | 41) NOTE: PLEASE SEE 4LC3-9 AND 25 WHICH IS SHOWN TO |
| | ROOM/AREA C4.202 YET THE PANEL SCHEDULE INDICATES ONE |
| | OF THESE FOR THIS LOCATION AND ONE OF THESE FOR A |
| | DIFFERENT LOCATION. THERE IS ALSO THE FACT THE J-BOX IS |
| | ALSO FED FROM THE ONE OF THESE CIRCUITS WHICH IS #25. |
| | IS THIS CORRECT FOR THE J-BOX? |
| | |
| | 42) NOTE: PLEASE SEE 4LD3-3, 22 AS BOTH ARE SHOWN ON |
| | PLANS, HOWEVER PLEASE SEE THAT THE PANEL SCHEDULE FOR |
| | 22 IS BLANK. |
| | |
| | 43) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| | STATIONS WHICH SHOW THE SAME CIRCUITING SUCH AS |
| | 5LA3-21, 23. PLEASE SEE 220.14(I) FOR LOADS PER YOKE. |
| | PLEASE PROVIDE INFORMATION ON HOW MANY RECEPTACLES ARE |
| | ON THE CIRCUITS AS SHOWN FOR KNOWN LOADS. THIS WAS GONE |
| | OVER IN ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR |
| | KNOWN LOADS AND LOADS FIGURED AT 180VA. THE REVIEW |
| | COMMENTS CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH |
| | QUESTIONS WERE RAISED. |
| | |
| | 44) NOTE: PLEASE SEE 5LA2- 34 WHICH ON THE PANEL |
| | SCHEDULE IT STATES ELECTRICAL ROOM A5.107 RECEPTACLES. |
| | HOWEVER THE PLANS SHOW A COMPLETELY DIFFERENT CIRCUIT |
| | WHICH FEEDS MANY OTHER LOCATIONS. THE CIRCUIT ON PLANS |
| | FOR THIS ROOM IS NOT #34. SEE THE FOLLOWING COMMENT. |
| | |
| | 45) NOTE: PLEASE SEE 5LA2-3 ON PANEL SCHEDULE WHICH |
| | STATES CORRIDOR LIGHTING. HOWEVER ON PLANS THIS FEEDS |
| | ROOM ABOVE WHICH IS A5.107, 5.103,5.104,203 ETC |
| | |
| | 46) NOTE: PLEASE SEE A1.014 ON PLANS SHOWS HA-1 HOWEVER |
| | THE DESIGNATION ON PANEL SCHEDULE IS NOT THE SAME. |
| | SHOWS A DIFFERENT ROOM. |
| | |
| | 47) NOTE: PLEASE SEE 1HA-12 ON PLANS AND PANEL SCHEDULE |
| | HOWEVER THIS IS NOT PART OF THE LCP. |
| | |
| | 48) NOTE: PLEASE SEE 410.8 A-D FOR MINIMUM LIGHTING |
| | FIXTURE CLEARANCES FROM COMBUSTIBLES IN CLOSETS WITH |
| | SHELVING. PLEASE SEE STORAGE CLOSETS A1.612,613.14. |
| | PLEASE PROVIDE EXACT SHELVING DIMENSION ON PLANS SO |
| | THAT THE CLEARANCES CAN BE DETERMINED. |
| | |
| | 49) NOTE: PLEASE SEE 1HA-2 WHICH THE PLANS , THE PANEL |
| | SCHEDULE AND THE LCP DO NOT CORRELATE. THE CIRCUITING |
| | ON PLANS SHOWS ONE LOCATION/ROOM WHICH IS THE GALLERY |
| | A1.306 YET THE PANEL STATES THIS CIRCUIT IS FOR |
| | EXTERIOR FIXTURES. THE LCP DOES NOT INDICATE ANY OF |
| | THESE. |
| | |
| | 50) NOTE: PLEASE REVISE FIXTURE SCHEDULE AND SUBMIT. |
| | FIXTURES FOR EXISTING LOCATION AND REVISED LOCATIONS ON |
| | PLANS CAN NOT BE DETERMINED AS CODE COMPLIANT WITH THE |
| | EXISTING REVISED CALCULATIONS PER 13-415.2. |
| | |
| | 51) NOTE: PLEASE SHOW LOCATIONS OF REQUIRED OVER RIDES |
| | ON THE 3RD FLOOR EAST END OF LIBRARY. REVISION 17 |
| | DELETED THE REQUIRED OVER RIDES BASED ON |
| | FURNITURE/SHELVING LAYOUT. ALL REVISED PLANS UP TO THIS |
| | LATEST REVISION STILL INDICATE EACH OF THE CIRCUITS |
| | WILL GO TO OVER RIDE SWITCHES HOWEVER NEW LOCATIONS |
| | WERE NOT SHOWN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 OF THE FBC. LOCATION |
| | REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS |
| | BEING OVER RIDDEN OR MEET EXCEPTIONS. |
| | |
| | 52) NOTE: PLEASE UPDATE ALL LCP. MANY OF THESE DO NOT |
| | LIST THE CIRCUITS ON THE PANEL SCHEDULES OR THE |
| | LOCATIONS LISTED ARE NOT CORRECT. |
| | |
| | 53) NOTE: PLEASE SEE 1HC-19 AS THIS IS ON PLAN AND |
| | SCHEDULE HOWEVER NOT ON LCP. |
| | |
| | 54) NOTE: PLEASE SEE LOBBY D1.003 WHERE ARE THE LIGHTS |
| | WHICH IS NOT PART OF THE PHOTO MUSEUM? FBC CHAPTER 10, |
| | NFPA- 101 7.8, 7.9. |
| | NEC CHAPTERS 2,3,4, GIVEN AS GENERAL SECTIONS. |
| | PLANS ARE BLANK. |
| | |
| | 55) NOTE: PLEASE SEE C1.102 AS THERE IS NO CIRCUIT |
| | LISTED OR SHOWN FOR LIGHTING. WHERE DOES THIS |
| | INTERCONNECT AND WITH WHICH CIRCUIT? |
| | |
| | 56) NOTE: PLEASE SEE 2HA-12 WHICH IS NOT SPECIFIC TO |
| | ROOMS AND AREAS. |
| | |
| | 57) NOTE: PLEASE SEE 2HA-19 WHICH IS ON PLANS, ON PANEL |
| | SCHEDULE HOWEVER LCP IS BLANK AND DOES NOT INDICATE. |
| | |
| | 58) NOTE: PLEASE SEE A2.210 AND .211 ROOMS. WHERE DO |
| | THE LIGHTS IN THESE TWO ROOMS CONNECT? THE PLANS APPEAR |
| | TO MAYBE CONNECT TO 2HA-47 HOWEVER BASED ON THE PANEL |
| | SCHEDULE THESE TWO ROOMS ARE NOT LISTED. |
| | |
| | 59) NOTE: PLEASE SEE 3HA-16 WHICH IS SHOWN ON PLANS, |
| | YET THERE IS NOTHING ON PANEL SCHEDULE OR LCP. |
| | |
| | 60) NOTE: PLEASE SEE 3HA-6 STATES ON THE PANEL SCHEDULE |
| | THIS FEEDS A3.009 AND A3.402 YET THE PLANS INDICATE |
| | A3.402 BEING FED FROM 3HA-8. PLEASE SEE OTHER LOCATIONS |
| | NOT SPECIFIC. |
| | |
| | 61) NOTE: PLEASE 3HA-8 WHICH IS NOT SPECIFIC. |
| | |
| | 62) NOTE: PLEASE COMPLETE PLANS WITH CIRCUITING, LOADS |
| | AND LIGHTING FOR STAGE AREA LIGHTING. PLANS SHOW *TO BE |
| | BY OTHERS* HOWEVER THAT WAS WHEN NONE OF THAT |
| | INFORMATION WAS KNOWN. THIS IS THE END OF THE BUILDING |
| | ALL OF THE LIGHTING, CIRCUITING, LOADS ETC ARE KNOWN AT |
| | THIS TIME WHICH NEEDS TO BE COMPLETE ON PLANS. |
| | 220,13-415.1.ABC.1.1, .1.3 ETC |
| | |
| | 63) NOTE: PLEASE SEE AREAS C3.110,.109,0309 ETC. THE |
| | NORMAL LIGHTING IN THIS AREA DOES NOT HAVE ANY CIRCUIT |
| | NOTED OR SHOWN. |
| | |
| | 64) NOTE: PLEASE SEE E2-4.1, LIGHTS IN CORRIDOR A4.009 |
| | WHICH DOES NOT INDICATE ANY CIRCUITING FOR NORMAL |
| | LIGHTING?? |
| | |
| | 65) NOTE: PLEASE SEE 4HC-12 WHICH IS LISTED ON THE LCP |
| | HOWEVER NOT ON PANEL SCHEDULE. |
| | |
| | 66) NOTE: PLEASE SEE 4HC-2 WHICH IS ON SCHEDULE FOR |
| | LIGHTING IN ELEVATOR LOBBY 5 AND 6; HOWEVER THIS SAME |
| | LOBBY AREA DOES NOT HAVE ANY CIRCUIT FOR THE LIGHTING |
| | ON PLANS. IN FACT THE LIGHTING ON PLANS IS ALL SHOWN AS |
| | EMERGENCY CIRCUITED LIGHTING HOWEVER NO CIRCUIT OR |
| | CONNECTION TO OTHER CIRCUITS IS SHOWN. |
| | THE CIRCUIT 4HC-2 ON PLANS IS ONLY FEEDING THE C4.105 |
| | ROOM AND ALSO THE TWO BATHROOMS C4.102,.103 WHICH DOES |
| | NOT COORDINATE WITH THE PANEL SCHEDULE. |
| | |
| | 67) NOTE: PLEASE SEE 4HC-10 WHICH IS ON PANEL SCHEDULE |
| | HOWEVER ON LCP. |
| | |
| | 68) NOTE: PLEASE SEE 5HA-3 WHICH IS LISTED ON THE LCP |
| | HOWEVER IT IS NOT ON THE PANEL SCHEDULE. ** PLEASE SEE |
| | THIS SHEET OF PLANS. E2-5.1, GO OVER PLANS. SEE |
| | COMMENTS BELOW. |
| | |
| | 69) NOTE: PLEASE SEE 5HA-17 WHICH STATES * OPEN WORK |
| | AREA A5.404 HOWEVER ON THE PLANS THIS IS COMPLETELY |
| | SEPARATE. A5.112,.104,.103. |
| | |
| | 70) NOTE: PLEASE SEE AREAS OF NORMAL LIGHTING A5.507, |
| | .506, .504,.501,.528,.503,.505,.508 ETC WHICH DO NOT |
| | SHOW ANY CIRCUITING ON PLANS. |
| | |
| | 71) NOTE: PLEASE SEE 5HB-5 WHICH IS SHOWN ON PLANS, YET |
| | THIS IS SHOWN AS A SPARE ON PANEL SCHEDULE. |
| | |
| | 72) NOTE: FEE BALANCE OF $1160.00 IS DUE BEFORE PICKING |
| | UP PLANS AND RESUBMITTING NEW REVISIONS. |
| | |
| | |
| | **** THIS IS NOT AN EXHAUSTED LIST OF ALL POSSIBLE |
| | ITEMS. THESE HAVE BEEN GIVEN AS EXAMPLES ONLY! THESE |
| | ARE NOT ALL ITEMS. |
| | |
| | |
| | |
| | |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |