| Plan Review Notes For Permit 06100574 |
| Permit Number |
06100574 |
|
| Review Stop |
E |
| Sequence Number |
41 |
|
| Notes |
| Date |
Text |
| 2009-03-30 16:49:56 | ** DENIED REVIEW/PASSED PROVISO ** | | | | | | REVISION FOR CAF?? | | | | | | | | | | | | 1) NOTE: SHEET E1-1.2 STAMPED FOR INSPECTIONS OF LAYOUT | | | OF ELECTRICAL ONLY. | | | NO OTHER ITEMS ON THIS SHEET REVIEWED FOR CODE | | | COMPLIANCE. | | | | | | 2) NOTE: PLANS SHOW THE LOCATION OF NEW PANEL HOWEVER | | | THE NEW TRANSFORMER AND MAIN ON THE LOAD SIDE OF THE | | | TRANSFORMER NEEDS TO BE SHOWN. COMPLIANCE WITH 110.26, | | | 240.24, 240.21, 450.9, ETC CAN NOT BE REVIEWED AT THIS | | | TIME. | | | RISER NOTES STATES PANEL TO BE LOCATED IN ROOM C1.402 | | | HOWEVER BASED ON SHEET E1-1.2 THE PANEL IS NOT IN THIS | | | SAME ROOM/LOCATION. | | | PLEASE BE SURE TO COORDINATE ALL SHEETS. | | | SHEET REDLINED. | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|