| Plan Review Notes For Permit 06100574 |
| Permit Number |
06100574 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-04-05 10:12:41 | ---------------DENIED------------------ | | | | | | GARAGE REVISIONS (7) SUBMITTED 3/16/07 | | | | | | 1. NEW MECHANICAL SHEETS SUBMITTED ARE MODIFYING | | | EXISTING SHEETS WHICH ALREADY COVER THE SCOPE OF | | | MECHANICAL WORK IN THE PERMIT SET OF PLANS. PLEASE | | | REVISE EXISTING SHEETS TO INCLUDE THE ADDED WORK OR | | | SHOW THE FULL SCOPE OF WORK TO BE PERFORMED IN THESE | | | AREAS ON NEW SHEETS WHICH WOULD REPLACE/SUPERCEDE | | | EXISTING SHEETS. | | | | | | 2. EQUIPMENT LOCATED IN PUBLIC GARAGES SHALL BE | | | INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR, OR A | | | MINIMUM OF 2 FEET HIGHER THAN THE HEIGHT OF THE TALLEST | | | VEHICLE, OR PROTECTED FROM MOTOR VEHICLE IMPACT. FBC,M | | | 304.5 | | | | | | 3. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL AND | | | INSTALLATION INSTRUCTIONS FOR C.O. SYSTEM. FBC,M 304.1 | | | | | | NOTE: A COMPLETE REVIEW OF THIS WORK CAN NOT BE | | | PERFORMED PRIOR TO THE INCORPORATION OF ALL MECHANICAL | | | WORK TO BE PERFORMED IN THESE AREAS AS STATED IN | | | COMMENT #1. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|