| Date |
Text |
| 2007-02-18 13:31:52 | 2007-02-18 13:31:52 |
| | |
| | *** PROVISO/REVISION *** |
| | |
| | |
| | ** THE FOLLOWING *PROVISO* WAS SET UP WITH CONDITIONS |
| | THAT ALL OF THE FOLLOWING BE REVISED, UPDATED AND |
| | SUBMITTED FOR REVIEW WITHIN 60 DAYS FROM ISSUANCE OF |
| | PERMIT. |
| | PLEASE SEE THAT MANY OF THE ITEMS BELOW BESIDES CODE |
| | RELATED ITEMS ARE MOSTLY BASED ON COORDINATION RELATED |
| | ISSUES. |
| | PLEASE SEE SOME OF THE NOTES ARE NEW AS SOME THINGS |
| | HAVE BEEN ADDED TO THESE PLANS WHICH WERE NOT ON |
| | PREVIOUS REVIEWED PLANS. |
| | THE SECTION OF THE FBC 106.1.2 MADE IN NOTES BELOW IS |
| | FROM THE 2004 FBC ADMINISTRATIVE SECTION AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH FOR * ADDITIONAL |
| | INFORMATION*. |
| | ** MANY OF THESE WILL NOT ONLY REQUIRE THE PARTIAL FOR |
| | EACH FLOOR, BUT ALSO THE *OVERALL* FLOOR SHEETS TO BE |
| | REVISED. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT THE WIND LOAD CALCULATIONS FOR |
| | SITE LIGHT POLES FOR COURTYARD AND ROOF TOP AREAS. |
| | THESE SHALL CONTAIN THE ORIGINAL SIGNATURE, DATE AND |
| | SEAL FROM THE ENGINEER OF RECORD. FS 471.025 AND TITLE |
| | BLOCKS ON EACH SHEET PER 61G15-23.002. |
| | |
| | 2) NOTE: PLEASE SEE THAT THERE MAY BE POSSIBLE STAIRS |
| | TO THE ROOF ON THE SOUTH SIDE OF THE BARREL ROOF FROM |
| | THE FOURTH LEVEL. THIS IS A BUILDING CODE REQUIREMENT |
| | AND PENDING ANY DECISION FROM THE CBA, LIGHTING, |
| | PHOTO-METRICS ETC WILL BE REQUIRED TO BE SUBMITTED AND |
| | REVISED FOR THOSE SHEETS AFFECTED BY THIS. |
| | THIS WOULD INVOKE LS 101 7.8 AND 7.9. |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHERE |
| | BATTERY BACK UP TYPE FIXTURES ARE BEING SHOWN WITH OC |
| | DEVICES OR SWITCHING. |
| | PLEASE SEE PREVIOUS NOTES WHICH REQUESTED BATTERY BACK |
| | UP FIXTURES OF SOME SORT IN MANY ROOMS; HOWEVER PLANS |
| | WERE REVISED IN MANY ROOMS TO INCLUDE A ZE FIXTURES, |
| | WHICH IF CONTROLLED AS SHOWN (SWITCHED) THEN THE LIGHT |
| | FIXTURE WHICH IS BATTERY BACK UP WOULD COME ON EACH |
| | TIME THE SWITCH OR DEVICE TURNS LIGHTING OFF. PLEASE |
| | SEE MOST ELECTRICAL ROOMS, ELEVATOR EQUIPMENT ROOMS, |
| | MECHANICAL ROOMS ETC. |
| | PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO |
| | CONTAIN A BATTERY BACK UP FIXTURE, HOWEVER THESE |
| | LOCATION ARE NOT TO HAVE LIGHTING REMAIN *ON* AS NL |
| | (NIGHT LIGHTS) 24 HRS A DAY. |
| | THESE LOCATIONS WHICH WILL REQUIRE A BATTERY BACK UP |
| | FIXTURE, BUT NOT FOR FIXTURES TO BE SWITCHED OR ON AS |
| | NL SHALL BE THE *MAIN ELECTRICAL ROOM IN GARAGE, MAIN |
| | MECHANICAL ROOM IN GARAGE, ALL ELEVATOR EQUIPMENT |
| | ROOMS, IT ROOM, FIRE PUMP ROOMS, BOTH MEZZANINE |
| | MECHANICALROOMS, THE MECHANICAL ROOM ON ROOF AND FIRE |
| | COMMAND ROOM. PLEASE SEE ALL OTHER SMALLER ELECTRICAL |
| | ROOMS WHICH CONTAIN ZE OR ZE2 FIXTURES ARE NOT REQUIRED |
| | TO CONTAIN A BATTERY BACK FIXTURE, BUT MAY. IF THEY DO |
| | CONTAIN A BATTERY BACK UP THESE SHALL NOT BE SWITCHED |
| | AND SHALL NOT BE ON 24/7. (700.12E). |
| | PLEASE GO OVER ALL OF THESE LOCATIONS ON PLANS AS MANY |
| | ROOMS DO SHOW THESE TYPE FIXTURES, HOWEVER NOT ALL. |
| | (PLEASE SEE REDLINED PLANS AS MANY OF THESE HAVE BEEN |
| | HIGH-LIGHTED BUT NOT ALL). |
| | PLEASE SEE DOME ROOM ABOVE THE ROOF TOP MECHANICAL ROOM |
| | DOES NEED A BATTERY BACK UP FIXTURE FOR EGRESS (STAIRS) |
| | HOWEVER SHOULD NOT CONTAIN NL FOR 24/7 OPERATION. MANY |
| | OF THESE WOULD CREATE A DIRECT CONFLICT WITH 700.12E OF |
| | THE NEC AND CHAPTER 13 OF THE FLORIDA ENERGY CODE. |
| | ** PLEASE CALL TO GO OVER OR TO COME IN AND GO THROUGH |
| | PLANS** |
| | |
| | 4) NOTE: PLEASE SEE MANY LOCATIONS ON PLANS WHICH |
| | INDICATE NIGHT LIGHTS (NL). THE AMOUNT OF THESE |
| | FIXTURES SHOULD BE REVIEWED AS THE AMOUNT IS OVER IN |
| | MANY LOCATIONS FOR THAT WHICH IS REQUIRED FOR LS 101 |
| | 7.8 AND 7.9. PLEASE SEE SOME AREAS WHICH CONTAIN NL |
| | WHICH ARE STILL BEING SHOWN SWITCHED FROM LOCAL |
| | SWITCHES. |
| | PLEASE SEE FOR EXAMPLE A.5.06. |
| | PLEASE SEE MANY LOCATIONS WHICH THESE NIGHT LIGHTS DO |
| | NOT SHOW ANY CONTROL OR CIRCUITING AND OR ARE IN |
| | CONFLICT AS THERE ARE OTHER FIXTURES WHICH ARE SHOWN ON |
| | THE NIGHT LIGHT CIRCUITS WHICH DO NOT CORRELATE WITH |
| | THE TYPE OF FIXTURES ON LEGENDS. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE STAIRS WHICH ONLY CONTAIN CONTROL |
| | FOR LIGHT AT ONE LOCATION EITHER AT THE TOP OR AT THE |
| | BOTTOM OF STAIRS. |
| | PLEASE SEE STAIR 12, STAIR 13. (PLEASE SEE STAIR 11 FOR |
| | EXAMPLE WHICH SHOWS BATTERY BACK UP FIXTURES BEING |
| | SWITCHED. (AS NOTED ABOVE. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE ELECTRICAL CIRCUITING WHICH HAS |
| | NOW BEEN ADDED TO THE ELEVATOR EQUIPMENT ROOM ON ROOF |
| | TOP. PLEASE SEE THE DEDICATED CIRCUITS AS REQUIRED PER |
| | 620.23 ARE THE SAME CIRCUITS AS SHOWN FOR THE FIRST |
| | FLOOR ELEVATOR EQUIPMENT ROOMS WHICH NOW HAVE CIRCUITS |
| | SHOWN FOR LIGHTING. |
| | PLEASE ALSO SEE THAT TWO SETS OF THE PLANS WHICH |
| | INDICATE THESE CIRCUITS TO PANEL 1-HEE DO NOT SHOW |
| | THESE CIRCUITS OR LOADS ADDED TO PANEL. |
| | PLEASE SEE ONE OF THE SETS OF PLANS DO SHOW THESE |
| | CIRCUITS ADDED TO PANEL SCHEDULE; HOWEVER NOT TO |
| | LOADS. |
| | PLEASE CORRELATE AND REVISE. PLEASE ALSO SEE NEXT |
| | NOTE. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE NEW ELECTRICAL FOR EQUIPMENT |
| | ADDED FOR THE ROOF TOP ELEVATOR EQUIPMENT ROOM WHICH |
| | WAS ADDED TO THESE PLANS AND TO PANEL 5-LEB ARE SHOWN |
| | ON PANEL SCHEDULE BUT THE LOAD CALCULATIONS WERE NOT |
| | REVISED OR ADJUSTED FOR THESE NEW LOADS. |
| | PLEASE ALSO SEE 620.23 AS THE NEW CIRCUIT 16 FOR THIS |
| | SAME PANEL FOR THE RECEPTACLE CIRCUIT SHOULD BE LABELED |
| | FOR THIS ELEVATOR EQUIPMENT ROOM AND NOT GENERAL |
| | RECEPTACLE CIRCUITS. |
| | FBC 106.1.2. |
| | |
| | 8) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHEETS |
| | 1 OF 14 AND 14 OF 14 WHICH DID NOT CORRELATE FOR 6TH |
| | AND 7TH LEVELS AND LIGHTING. THESE ITEMS WERE CHANGED |
| | IN MEETING WITH ENGINEER. |
| | PLEASE ALSO SEE THE SHEET 4 OF THE FLORIDA ENERGY CODE |
| | INPUT DATA REPORT WHICH SHOWS *MANUAL CONTROLS FOR TWO |
| | AREAS. |
| | PLEASE SE THIS WAS ALSO CHANGED BY THE ENGINEER IN |
| | MEETING. |
| | THESE SHEETS SHOULD BE REVISED FOR THESE ITEMS AND FOR |
| | ANY AND ALL CHANGES MADE FOR FIXTURES IN MANY ROOMS AS |
| | NOTED ABOVE IN OTHER NOTES. |
| | FBC 106.1.2 |
| | FBC 13-415.1.AB.1, 13-415.2 |
| | |
| | 9) NOTE: PLEASE SEE FIRST FLOOR CITY HALL SECTION WHICH |
| | SEEMS TO BE MISSING A 3-WAY SWITCH FOR MAIL/RECEIVING |
| | ROOM. |
| | |
| | 10) NOTE: PLEASE SEE 3-WAY SHOWN ON E 2-2.2 WHICH IS |
| | NOT SHOWN ON E2-1.4 FOR THE SAME LOCATION. (REDLINED) |
| | |
| | 11) NOTE: PLEASE SEE AS NOTED ABOVE A BATTERY BACK UP |
| | FIXTURE WILL BE REQUIRED IN THE IT ROOM OF SOME SORT. |
| | LS 101 7.8, 7.9. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THAT MANY OF THE REVISED LIGHTING |
| | PLANS DO NOT CORRELATE WITH THE REVISED PHOTO-METRICS |
| | OR MANY OF PHOTO-METRICS SHEETS WERE NOT REVISED. |
| | PLEASE SEE STAIR 12, WHICH SHOWS DIFFERENT LIGHTS AND |
| | LOCATIONS ON LIGHTING PLANS THAN THAT OF THE SAME STAIR |
| | ON BOTH THE NORMAL AND EMERGENCY PHOTO-METRICS. PLEASE |
| | SEE THE PHOTO-METRICS SHOULD COORDINATE WITH ALL OTHER |
| | FIXTURES, TYPES ETC. |
| | PLEASE SEE PREVIOUSLY NOTED DOUBLE LIGHT FIXTURES IN |
| | STAIRS. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE:AS PREVIOUSLY NOTED PLEASE CORRELATE AND |
| | REVISE ALL PHOTO-METRICS FOR STAIR DESIGNATIONS. PLEASE |
| | SEE THERE ARE MANY SHEETS WHICH STILL INDICATE THE OLD |
| | DESIGNATIONS. PLEASE SEE SOME SHEETS SHOW THE TABLES |
| | SHOW ONE DESIGNATION AND THE PLANS SHOW ANOTHER. PLEASE |
| | SEE SOME TABLES SHOW DESIGNATION, AND THEN THE SHEETS |
| | FOR THOSE STAIRS ARE BLANK? |
| | PLEASE SEE MISSING STAIR 6 FOR BOTH NORMAL AND |
| | EMERGENCY. |
| | PLEASE SEE TWO OF THE SETS FOR PHOTO-METRICS ARE |
| | DIFFERENT FROM THE THIRD SET WHERE SOME OTHER |
| | DESIGNATIONS WERE REVISED, BIT THE OTHER TWO SETS |
| | CONTAIN SOME SHEETS WHICH WERE REVISED AND SOME WHICH |
| | WERE NOT. PLEASE SEE THAT EVEN SOME OF THE REVISED |
| | SHEETS FOR DESIGNATIONS DO NOT CORRELATE. |
| | PLEASE SEE SHEETS 9-3.0 AND 9-3.2 WHICH BOTH APPEAR TO |
| | BE THE SAME SHEET. THE SHEET 9-3.2 SHOULD BE THE |
| | PARTIAL FOR AREA. |
| | ** PLEASE SEE THAT MANY OF THESE AREAS ARE REDLINED AND |
| | HIGH-LIGHTED ON PLANS. |
| | ** PLEASE SEE TWO SETS WHICH THIS IS AN ISSUE FOR |
| | SHEETS 9-5.0 AND 9-5.2 |
| | FBC 106.1.2 |
| | |
| | 14) NOTE: PLEASE SEE REDLINED DIVISION 16 SPECS FOR |
| | COLOR CODING FOR 277/480V SYSTEM. |
| | * BROWN, PURPLE, YELLOW* |
| | |
| | 15) NOTE: IF THE FIXTURE DESIGNATIONS ARE GOING TO BE |
| | SHOWN ON PHOTO-METRICS, THEN PLEASE CORRELATE WITH THE |
| | LIGHTING PLANS. THERE ARE NUMEROUS FIXTURES WHICH DO |
| | NOT CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 16) NOTE: LIGHTNING PROTECTION WILL BE UNDER SEPARATE |
| | PERMIT, HOWEVER MAY USE THESE PLANS TO REFERENCE. |
| | |
| | 17) NOTE: PLEASE SEE THE FUTURE BUILD OUT FOR IT WILL |
| | BE UNDER A SEPARATE PERMIT WHICH WILL REQUIRE |
| | SUBMITTALS FOR ALL EQUIPMENT BEING INSTALLED IN THIS |
| | ROOM ALONG WITH PLANS, PERMIT APPLICATIONS AND FEES. |
| | |
| | 18) NOTE: PLEASE SEE THE LOW VOLTAGE SYSTEMS ARE UNDER |
| | A SEPARATE PERMIT, PLANS AND FEES. PLANS ARE TO BE |
| | SUBMITTED AT A LATER DATE BEFORE INSTALLATION BEGINS. |
| | THESE PLANS REFLECT CONDUIT LOCATIONS ONLY. |
| | |
| | |
| | ** PLEASE KNOW AS MANY OF THESE ITEMS ARE REDLINED OR |
| | HIGHLIGHTED ON PLANS, THIS IS IN NO WAY ALL POSSIBLE |
| | LOCATIONS. PLEASE REVIEW SAID PLANS. |
| | |
| | ** PLEASE CALL TO SET UP A TIME TO GO OVER SOME |
| | POSSIBLE ALTERNATIVES FOR SOME OF THE ITEMS ABOVE. |
| | |
| | IF THERE ARE ANY QUESTIONS OR IF THE NOTES TYPED ARE |
| | NOT CLEAR IN ANY WAY, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | ** ALL PLANS, ALL SETS, ALL SUBMITTALS, SPEC BOOKS |
| | STAMPED. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-18 08:14:17 | 2007-02-18 08:14 |
| | CONTINUING TO PROCESS, NOTES TO FOLLOW. |
| 2007-02-16 07:01:13 | 2007-02-16 07:01:13 |
| | IN REVIEW |
| 2007-02-15 21:14:22 | 2007-02-15 21:14:22 |
| | ** REVIEW TO CONTINUE ON 2/16, PROVISO NOTES TO FOLLOW. |