| 2008-11-10 14:31:17 | |
| | |
| | |
| | ** DENIED REVISION ** |
| | |
| | 1) NOTE: PLEASE SUBMIT THE RIGHT OF WAY STREET LIGHTING |
| | UNDER A SEPARATE PERMIT. THESE ARE NOT PART OF THE BASE |
| | BUILDING LEGAL ADDRESS OR ELECTRICAL SYSTEMS. |
| | PLEASE BE SURE THE FIXTURE INFORMATION ON PLANS IS |
| | COMPLETE WITH THE TYPE OF FIXTURE, THE WATTAGE, THE |
| | VOLTAGE ETC. THE PLANS CONTAIN NOTES WHICH STATE |
| | RECEPTACLES ON POLE HOWEVER NO DETAIL IS SHOWN ON HOW |
| | THESE WILL INSTALLED OR WIRED. ARE THESE APART OF THE |
| | POLE FROM THE MANUFACTURE? |
| | 215,300,310.16,110.3,240.4, ETC |
| | FBC 105.1. |
| | |
| | 2) NOTE: THE PLANS WERE NOT ROUTED TO THE BUILDING PLAN |
| | REVIEWER AS NO WIND LOAD INFORMATION/CALCULATIONS WERE |
| | SUBMITTED FOR REVIEW. IN THE INTEREST OF TIME THIS |
| | REVIEWER IS ONLY PLACING NOTES FOR INFORMATION WHICH |
| | WILL BE NEEDED FOR THE STRUCTURAL REVIEW. THE WIND LOAD |
| | CALCULATIONS NEED TO SHOW THE POLE, STRUCTURAL |
| | COMPONENTS, THE EPA (EFFECTIVE PROJECTED AREA) OF THE |
| | FIXTURE OR FIXTURES. THESE WILL NEED TO BE COMPLETE |
| | WITH TITLE BLOCKS, ORIGINAL SIGNATURE, DATE AND RAISED |
| | SEAL BY A FLORIDA LICENSED AND REGISTERED ENGINEER. |
| | FBC TABLE 1609 |
| | FS 471.025 |
| | FAC 61G15-23.002 |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |