| Date |
Text |
| 2007-01-26 13:36:28 | 1. SIAMESE CONNECTION DISPLAYED ON PAGE FP1-1.2 IS NOT |
| | NEEDED AND SHOULD BE STRICKEN FROM THE PLANS. THE PLAN |
| | REVIEW PERMIT RESPONSES INCLUDE NOW THREE SIAMSE |
| | CONNECTIONS INSTEAD OF THE FIVE PREVIOUSLY SHOWN. 2. NO |
| | FIRE ALARM EQUIPMENT SHOWN IN MACHINE ROOM A6.102 ON |
| | PAGE FA1-6.0. THIS IS AN EXISTING COMMENT. |
| | 3. ONLY TWO FIRE ALARM STROBES ARE PRESENT IN THE |
| | GARAGE ON PAGE FA1-6.0. THIS IS ALSO AN EXISTING |
| | COMMENT. |
| | 4. SMOKE DETECTOR STILL MISISNG IN VOICE DATA CLOSET |
| | C3.104 ON PAGE FA1-3.0. THIS IS AN EXISTING COMMENT. 5. |
| | A VISUAL REPRESENTATION OF THE SMOKE CONTROL PANEL |
| | SHALL BE SUBMITTED AT TIME OF SHOP DRAWING SUBMITTAL. |
| | THIS SMOKE CONTROL PANEL SHALL DISPLAY A GRAPHIC |
| | REPRESENTATION OF THE BUILDING SYSTEM TO INCLUDE HAND, |
| | ON, AND AUTO CONTROLS. |
| | 6. ITEMS # 9, 11, 12, 20, 23, COULD NOT BE CLEARED FRON |
| | LIST. SOME ITEMS CAN BE PICKED UP AT SHOP DRAWING |
| | SUBMITAL TIME SO LONG AS THEY ARE PROPERLY IDENTIFIED. |
| | 7. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE |
| | PROPERLY SATISFIED WITH THE ELECTRICAL PLAN REVIEWER. |
| | 8. PLEASE REMEMBER THAT THE ELVATION OF FLOOR LEVELS ON |
| | BOTH SIDES OF AN EXIT DOOR CANNOT EXCEED 1/2 ". |
| | |
| | PLANS WILL BE APPROVED PROVISO AND ALL WORK AT THE SITE |
| | IS SUBJECT TO FIELD INSPECTION AND APPROVAL. THIS |
| | APPROVAL DOES NOT RELLIEVE RESPONSIBLE PERSONS OR FIRMS |
| | FROM OBTAINING ANY OTHER GOVERNMENTAL REVIEWS OR |
| | APPROVALS. |