| 2008-11-25 16:32:06 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM |
| | PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08 |
| | INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED |
| | SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS |
| | REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW |
| | REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD |
| | IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED |
| | WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW |
| | REVISION CAN BE LOCATED. -- THIS HAS BEEN INDICATED IN |
| | A PREVIOUS REVISION REVIEW. |
| | |
| | 2. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS |
| | SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES |
| | REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET |
| | SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION |
| | 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER |
| | SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED |
| | AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD |
| | AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN |
| | BE LOCATED. -- THIS HAS BEEN INDICATED IN A PREVIOUS |
| | REVISION REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |