| Date |
Text |
| 2006-12-23 17:38:49 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE |
| | INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR |
| | CERTIFICATION AND SERVICE. |
| | ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE |
| | BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. |
| | ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE |
| | THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE |
| | FLOOR. |
| | |
| | 4. OK |
| | |
| | 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY |
| | SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 |
| | (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE |
| | NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS |
| | REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE |
| | NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE |
| | INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. |
| | ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER |
| | DIAGRAMS. |
| | ****RESPONSE NOTED, BUT THE CLEANOUT SHOWN ON P3-3.0 |
| | DETAIL 1 AS SHOWN IS CORRECT, BUT IT'S NOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CORRELATE INFORMATION ON ALL SHEETS. |
| | ALSO SEE RISERS P/1, P/7 & P/8. |
| | |
| | 6.OK |
| | 7.OK |
| | 8.OK |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | |
| | 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, |
| | INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS |
| | DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. |
| | SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY |
| | OVERFLOW SCUPPERS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE |
| | SUBMITTED. |
| | ****RESPONSE NOTED, BUT THE CALCULATIONS ARE NOT |
| | CORRECT. NO VERTICAL CONTRIBUTION IS SHOWN FOR THE |
| | LOWER ROOFS. (A1 THRU A4, A7 THRU A9, E1 THRU E4, E7 |
| | THRU E9, E1 THRU E4, & H1 THRU H4). THE WALL AT COL. |
| | LINES 4&7 BETWEEN COL. LINES A&D, CALCULATIONS INDICATE |
| | 7', WHICH IS SUPPOSED TO BE 1/2 THE WALL HEIGHT. BY |
| | LOOKING AT A SECTION OF THE WALL, THE HEIGHT IS 20' AND |
| | 1/2 THE WALL HEIGHT SHOULD BE 10'. (SEE A4-2.0WHICH |
| | SHOW THE WALL TO BE 18', AND IF ITS SIMILAR TO DETAIL 3 |
| | ON SHT A5-1.1 WILL HAVE A 2' PARAPET WALL ON TOP OF THE |
| | ROOF LINE. PLEASE RECHECK ALL CALCULATIONS FOR THE ROOF |
| | AREAS. |
| | |
| | 15. OK |
| | 16. OK (SHOWN ON SHT P2-1.0U) |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | |
| | 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND |
| | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, |
| | VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS |
| | THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT |
| | SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE |
| | ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT |
| | REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT |
| | REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS |
| | SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE |
| | BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0 |
| | RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM |
| | C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT |
| | AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT |
| | THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR |
| | PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED |
| | IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING |
| | FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE |
| | FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108, |
| | AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF |
| | STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT |
| | THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM |
| | D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET |
| | ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE |
| | SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.- |
| | SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE |
| | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| | (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS |
| | INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.- |
| | A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE |
| | FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE |
| | MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR |
| | PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE |
| | SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER |
| | DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH |
| | LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE |
| | FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT |
| | FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS |
| | REQUIRED AT THE BASE OF RISER P/8-ALL RISER |
| | DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER |
| | DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY |
| | AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3, |
| | 708.3.4, 708.3.5, 100.2.1. |
| | |
| | 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & |
| | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, |
| | & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE |
| | SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION |
| | 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT |
| | INDICATED. |
| | ****RESPONSE NOTED, BUT THE GARAGE STORM INDICATES A |
| | TOTAL OF 10,498SF. THE TOTAL AREA WITHOUT ANY VERTICAL |
| | WALL/PARAPET CONTRIBUTION IS 23,663SF. PLEASE |
| | RECALCULATE THE SQUARE FOOTAGE DRAINING INTO EACH |
| | DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALL INCLUDING |
| | PARAPETS, AS WELL AS ALL AREAS FROM ROOFS THAT DRAIN |
| | ONTO THE ROOF FROM ABOVE, (SEE STAIRWELL ROOFS & |
| | ELEVATOR), IN CALCULATIONS. -THE TRENCH DRAINS SHOW |
| | NO SF CONTRIBUTING TO THE TOTAL SF. INDICATE THE |
| | LOCATIONS OF THE DOWNSPOUTS FROM THE ROTUNDA/MECHANICAL |
| | ROOF. IF THE LOCATION IS THE SAME AS SHOWN ON THE |
| | ARCHITECTURAL PLANS, PLEASE EXPLAIN THE REASONING FOR |
| | DIVIDING THE UPPER ROOF CONTRIBUTION TO TWO ROOF DRAINS |
| | ON EACH SIDE OF THE BUILDING, WHEN ACTUALLY THE TOTAL |
| | AREA WILL DRAIN TO ONE DRAIN ON EACH SIDE. THIS IS ALSO |
| | A CONCERN FOR THE LOWER ROOF (FIRST STORY)ROOF DRAINS |
| | ( 1736SF). PLEASE CLARIFY. |
| | |
| | 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL |
| | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW |
| | PROTECTION ETC. SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, |
| | NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, |
| | DISHWASHERS, & WASH MACHINES IF FIXTURES ARE |
| | PROVIDED). |
| | ****RESPONSE NOTED, BUT THE VALVES ON ALL DOWN-FEED |
| | WATER LINES ARE MISSING FROM MANY LAV SUPPLY LINES, |
| | SOME TOILET ROOMS, SS, ETC. SECTION 106.1(4). |
| | |
| | 39. OK |
| | |
| | 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE |
| | SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE |
| | BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS |
| | 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE |
| | NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS |
| | SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE |
| | ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS). |
| | ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND |
| | PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE |
| | SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF |
| | RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED, |
| | NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE |
| | ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS |
| | SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES |
| | NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM |
| | OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & |
| | ROOF PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS |
| | FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH |
| | CORRECTIONS. |
| | |
| | 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO |
| | RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID |
| | IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY |
| | PIPE SIZES. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT ISSUE NOT ADDRESSED. |
| | |
| | 3B. SHTS P1-1.1U & P2-1.0U DETAIL #6 THE SINK SHALL NOT |
| | DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE |
| | DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| | TOILET ROOM FIXTURES. SECTION 909.1. |
| | ****RESPONSE NOTED, BUT THE PIPING HAS NOT BEEN CHANGED |
| | ON SHT P1-1.0U |
| | |
| | 4B. OK |
| | |
| | 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & |
| | P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN |
| | AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION |
| | OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. |
| | 708.3.3, 708.3.4, 708.3.5. |
| | ****RESPONSE NOTED, BUT C/O'S ARE NOT SHOWN ON SHTS |
| | P3-1.0 & P3-2.0. |
| | |
| | 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND |
| | ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & |
| | P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. |
| | SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" |
| | CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE |
| | Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. |
| | WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE |
| | SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD |
| | CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD |
| | CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN |
| | THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE |
| | NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH |
| | STACK. COMMENT HAS NOT BEEN ADDRESSED. |
| | |
| | 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 |
| | RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| | RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE |
| | INFORMATION. SECTION 106.1.1 & TABLE 1106.3. |
| | ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED |
| | ON SHTS P1-3.3, & P1-4.3. |
| | |
| | 8B. OK |
| | 9B. OK |
| | 10B. OK |
| | 11B. OK |
| | |
| | 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE |
| | 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL |
| | 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE |
| | FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" |
| | SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN |
| | OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR |
| | PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. |
| | ****RESPONSE NOTED. NOTE DELETED, BUT COMMENT NOT |
| | ADDRESSED FOR OFFSETS AND VENTING. -VENTING ON ALL |
| | RISERS SHALL REFLECT THE VENTING ON THE FLOOR PLAN. |
| | (ALL VENTING NOT SHOWN ON THE FLOOR PLAN), AND ON THE |
| | ENLARGED PLUMBING PLANS FLOOR PLAN. |
| | |
| | 13B. OK |
| | 14B. OK |
| | |
| | 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - |
| | INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT |
| | SHOWN. |
| | |
| | 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE |
| | NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS |
| | IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE FLOOR DRAIN IN THE |
| | ACCESSIBLE STALL HAS NOT CHANGED TO REFLECT THE CHANGE |
| | IN THE RISER DIAGRAM. |
| | |
| | 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING |
| | LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE |
| | SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, |
| | SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE |
| | D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING |
| | ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO |
| | THE BLDG. DRAIN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT A DETAIL HAS NOT BEEN |
| | SUBMITTED. ALSO EXPLAIN THE 3" SANT. LINE FROM THE |
| | DRINKING FOUNTAINS TO THE MEN'S ROOM D1/101.-THE |
| | FLOOR DRAIN PIPING APPEARS TO BE ABOVE THE SLAB. PLEASE |
| | CLARIFY. |
| | |
| | 18B. OK |
| | |
| | 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT |
| | DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET |
| | ROOM. SECTION 909.1. |
| | ****RESPONSE NOTED. CORRECTED, BUT NOT CORRECTED ON SHT |
| | P1-1.1U. PLEASE CORRECT TO REFLECT RISER AND DETAIL. |
| | |
| | 20B. OK |
| | 21B. OK |
| | |
| | 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR |
| | PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT STILL NO WATER SUPPLY TO WATER |
| | HEATERS. |
| | |
| | 23B. OK |
| | 24B. OK |
| | 25B. OK. |
| | |
| | 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. |
| | PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER |
| | DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU |
| | BATHROOM FIXTURES. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT STILL SHOWS PIPING OUT THE SIDE |
| | OF 1ST DF. |
| | |
| | 27B. OK |
| | 28B. OK |
| | 29B. OK |
| | |
| | 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH |
| | LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS |
| | NO PIPING. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT RISER SHOWS P1 RISER BETWEEN |
| | W/C'S & LAVS, WHEREAS THE FLOOR PLAN SHOW THE RISER |
| | BETWEEN W/C'S. CORRELATE RISER AND FLOOR PLAN. |
| | |
| | 31B. OK |
| | 32B. OK |
| | 33B. OK |
| | |
| | 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED |
| | ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR |
| | LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR |
| | DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION |
| | 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 |
| | SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE |
| | BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND |
| | 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C |
| | STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. |
| | SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. |
| | SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION |
| | 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR |
| | DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & |
| | 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS |
| | SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES |
| | NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR |
| | FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE |
| | FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT |
| | REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE |
| | BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION |
| | DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A |
| | 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF |
| | THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK |
| | P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS |
| | INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104 |
| | DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - |
| | PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS |
| | HAVE NOT BEEN ADDRESSED. |
| | |
| | 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL |
| | SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN |
| | ON THE RISER DIAGRAMS. |
| | |
| | 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT |
| | THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING |
| | FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE |
| | BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN |
| | SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - |
| | PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE |
| | FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES |
| | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| | INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL |
| | 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS |
| | INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| | INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE |
| | FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT |
| | REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF |
| | C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - |
| | PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN |
| | UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT |
| | VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT |
| | BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. |
| | - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO |
| | F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A |
| | DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN |
| | AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. |
| | - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO |
| | BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT |
| | ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES |
| | NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL |
| | DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS |
| | REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING |
| | TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101. |
| | PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES |
| | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| | INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS |
| | A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. - |
| | PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN. |
| | - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED |
| | AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES |
| | NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 |
| | SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM |
| | D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE |
| | INFORMATION. |
| | |
| | 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| | TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION |
| | 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF |
| | THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM |
| | OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH |
| | P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING |
| | TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. |
| | FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & |
| | P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON |
| | RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT |
| | REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE |
| | OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS |
| | A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE |
| | OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE |
| | LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & |
| | A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - |
| | PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR |
| | PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| | ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| | PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE |
| | FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE |
| | FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE |
| | FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 38B. OK |
| | |
| | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI |
| | REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF |
| | REGULATOR. |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED |
| | |
| | F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT |
| | DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 |
| | BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS |
| | QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT |
| | 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" |
| | PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA |
| | DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS |
| | APPROXAMATLY 180'. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE |
| | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. |
| | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE |
| | MODEL NUMBER. LISTING INFORMATION REQUIRED. |
| | |
| | H. NA |
| | I. NA |
| | |
| | 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH |
| | FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER |
| | DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. |
| | SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR |
| | PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET |
| | ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, |
| | JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - |
| | INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH |
| | RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| | ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR |
| | PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON |
| | ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY |
| | LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER |
| | DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103. |
| | (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING |
| | ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS |
| | A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON |
| | RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS |
| | SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT |
| | SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8 |
| | STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION |
| | 106.1.1. |
| | |
| | 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON |
| | THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN |
| | ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, |
| | AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 |
| | TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO |
| | TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & |
| | RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT |
| | FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| | ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST |
| | FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS |
| | C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES |
| | OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY |
| | RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON |
| | RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE |
| | FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, ( |
| | 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR |
| | PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR |
| | 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1. |
| | PLEASE CORRELATE RISER AND FLOOR PLANS. |
| | |
| | 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND |
| | SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT |
| | REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - |
| | RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT |
| | SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO |
| | FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF |
| | LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET |
| | PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT |
| | INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE |
| | CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, |
| | 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES |
| | PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE |
| | ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT |
| | REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT |
| | THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE |
| | 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING |
| | COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT |
| | THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS |
| | INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A |
| | 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS, |
| | BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL), |
| | ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT |
| | 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3. |
| | |
| | 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS |
| | REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES |
| | "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL |
| | AND SIGNATURE" |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF |
| | AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. |
| | 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS |
| | REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. |
| | UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. |
| | PLEASE RESEAL PLANS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. |
| | 61G1-16.004(1) & FS 481.319. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION |
| | REQUIRED IN 61G1-16.004. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE |
| | REQUIRED ON PLANS. SECTION 106.1.1. |
| | ****NO RESPONSE. THIS INFORMATION SHALL BE SUBMITTED AS |
| | A REVISION PRIOR TO APPLICATION, OR WITH THE |
| | APPLICATION FOR IRRIGATION PERMIT - NEW COMMENT, NO |
| | CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK AS |
| | REQUIRED BY 61G1-16.004(2) & FS 481.319. |
| | |
| | 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND |
| | FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 |
| | ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES |
| | ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF |
| | DRINKING FOUNTAINS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD |
| | FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER |
| | TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| | UPDATE FIXTURE COUNT. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH |
| | FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY |
| | 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. |
| | TABLE 403.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST |
| | FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, |
| | BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| | REQUIRED. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD |
| | FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, |
| | BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| | REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. |
| | PLEASE CORRECT INFORMATION. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH |
| | FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT |
| | THE FIXTURE COUNT. TABLE 403.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN |
| | OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE |
| | POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT |
| | LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR |
| | E-MAIL [email protected]. |
| | ****PER ARCHITECT, NO RESTURANT WILL BE IN THE LIBRARY. |
| | THIS WAS INDICATED AS A RESTURANT FOR OCCUPANCY |
| | CALCULATIONS ONLY. THERE WILL BE A CAFE IN THE LIBRARY |
| | WITH NO FOOD PREPARATION. |
| | |
| | 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE |
| | CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED |
| | PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% |
| | REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. |
| | PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO |
| | RESPONSE, NOT ADDRESSED. |
| | |
| | 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS |
| | ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE |
| | SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT |
| | IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, |
| | BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF |
| | DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE |
| | RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO |
| | ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT |
| | COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 |
| | - 5/E THRU H). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE |
| | CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, |
| | INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO |
| | THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF |
| | LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS |
| | WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS |
| | IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR |
| | TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS |
| | 1106.1, 1106.2, 1106.3, 1106.4. |
| | ****NO RESPONSE NOTED. PRIMARY AND SECONDARY ROOF DRAIN |
| | CALCULATIONS WERE NOT FOUND. |
| | |
| | 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL |
| | INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND |
| | INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE |
| | OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. ****NO |
| | RESPONSE, NOT ADDRESSED. |
| | |
| | 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA |
| | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE |
| | FOR THE URINAL. SECTION 11-4.18.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. (SHOWS 2'2"). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA |
| | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 66B. SHT A6-3.1 DETAIL 2, SHOW A TURNING AREA IN THE |
| | LOCKER ROOM AREA. SECTION 11-4.2.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 67B. SHT A6-3.1 DETAILS 1, 3, 4 & 5, SHOW THE TURNING |
| | AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA |
| | IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| | TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE |
| | URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS |
| | C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, |
| | A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE |
| | PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE |
| | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS |
| | REQUIRED IN SECTION 1210.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 |
| | & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE |
| | INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS |
| | COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS |
| | REQUIRED IN SECTION 1210.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | DETAIL #1 |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | DETAIL #2 |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | DETAILS #1 - #2 - #3 |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING |
| | FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.7 CURBS |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, |
| | A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH |
| | THE FOLLOWING |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| | REQUIRED) |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | *************NEW COMMENTS************* |
| | |
| | 1C. SHT P9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | |
| | 2C. SHT P9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH |
| | THE FOLLOWING: |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | |
| | 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE |
| | ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR |
| | INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED |
| | LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR |
| | REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6721 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |