| 2006-12-26 13:25:55 | DENIED: |
| | RESPONSE TO COMMENTS DATED 11-07-06: |
| | |
| | COMMENT 1:OK |
| | COMMENT 2A & 2B:OK |
| | |
| | COMMENT 2C:RESPONSE INDICATES THE CAPACITY OF THE |
| | FUEL STORAGE TANK LOCATED ON THE FIRST FLOOR IS 500 |
| | GALLONS. THE SUBMITTAL BOOK REFLECTS (2) DAY TANKS ONE |
| | WITH THE CAPAPCITY OF 100 GALLONS AND THE SECOND ONE |
| | WITH A CAPACITY OF 150 GALLONS.PLEASE SUBMIT THE |
| | CORRECT SUBMITTAL FOR THE DAY TANK. |
| | |
| | COMMENT 3:OK |
| | |
| | COMMENT 9:OK |
| | |
| | COMMENT 10:OK |
| | |
| | COMMENT 11:OK |
| | |
| | COMMENT 12:OK |
| | |
| | COMMENT 13:OK |
| | |
| | COMMENT 14:OK |
| | |
| | COMMENT 15:OK |
| | |
| | COMMENT 16:RESPONSE INDICATES FIRE RATINGS ARE NOT |
| | REQUIRED FOR ELECTRICAL RM.SMOKE RATING IS INDICATED |
| | FOR THE MECHANICAL ROOM AND A 1 HR RATING FOR THE |
| | ELEVATOR EQUIPMENT RM.PER 2004 FMC 607.8,SMOKE |
| | DAMPERS, FIRE DAMPERS AND COMBINATION DAMPERS ARE TO BE |
| | IDENTIFIEDON THE BUILDING PLANS.PLEASE NOTE, LIFE |
| | SAFETY PLANS IDENTIFY CERTIAN WALLS/PARTITIONS AS |
| | HAVING A FIRE, SMOKE OR FIRE/SMOKE RATING THAT ARE NOT |
| | REFLECTED ON THE ARCHITECTURAL PLANS.PLEASE CORRELATE |
| | LIFE SAFETY, ARCHITECTURAL AND MECHANICAL PLANS. PLEASE |
| | SEE ?ADDITIONAL COMMENT #21?. |
| | |
| | COMMENT 17:OK |
| | |
| | COMMENT 18:OK |
| | |
| | COMMENT 19:OK |
| | |
| | COMMENT 20:OK |
| | ADDITIONAL COMMENTS: |
| | |
| | 21.THE FOLLOWING PLAN SHEET & ROOM NUMBERS ARE |
| | MISSING DAMPERS AS REQUIRED PER 2004 FMC 607.5.4 & |
| | 607.5.4.1: |
| | |
| | DWG M1-1.1; RM# - A1.014, A1.118, A1.110 |
| | DWG M1-2.1; RM# - C1.101, D1.108, A1.110, D1.111. |
| | |
| | PLEASE ALSO NOTE ON DWG #M1-1.2, THE OUTSIDE AIR INTAKE |
| | TO THE WEST EXTERIOR WALL.PER 2004 FMC 401.5.1, |
| | INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT |
| | FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS |
| | STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS. |
| | |
| | DWG M1-2.1 CORRIDOR A2.010, 38/18 & 12/10 DUCT,RM # |
| | A2.104, A2.108, A2.407, A2.08, A2.409 |
| | DWG M1-2.2 RM# C2.101, C2.219, D2.108 |
| | DWG M1-3.1 CORRIDOR A3.008, A3.012, A3.406, A3.308, |
| | A3.706, C3.414 RM# A3.107, A3.106, A3.421, A3.420, |
| | A3.105, A3.104, A3.304, A3.205, C3.314, C3.413, A3.705, |
| | A3.603, A3.115, A3.514, A3.513 |
| | DWG M1-3.2 CORRIDOR C3.417, C3.407, C3.426, RM# C3.418, |
| | C3.310, C3.309, C3.402, C3.107,C3.101 |
| | DWG M1-4.1 CORRIDOR A4.009, A4.008, A4.007 RM#A4.415, |
| | A4.101 & F/D FROM RM# A4.416. |
| | DWG M1-4.2 RM# C4.106, C4.104.PLEASE NOTE, MECHANICAL |
| | FLOOR PLAN DOES NOT MATCH THE LIFE SAFETY PLAN FOR THIS |
| | PARTICULAR FLOOR.THE VOICE DATA RM & ELECTRICAL RM |
| | ARE NOT INDICATED ON THE MECHANICAL SHEET. |
| | |
| | DWG M1-5.1 CORRIDOR A5.009, A5.008, A5.007 RM# A5.303, |
| | A5.203, A5.101, A5.507, A5.107, A5.416 |
| | |
| | 22.PLAN SHEET M1-1.0 KEY NOTE 1 SPECIFIES THE |
| | CONDENSATE TO MOP SINK IN THE GARAGE AREA.PER CITY |
| | CODE SEC. 90-125(5) CONDENSATE SHALL NOT TERMINATE INTO |
| | THE SANITARY.PLAN SHEET P1-10U INDICATES THE |
| | CONDENSATE TO A DRYWELL WHICH IS CODE COMPLIANT. PLEASE |
| | CORRELATE MECHANICAL PLAN WITH PLUMBING PLAN. |
| | |
| | ADDITIONAL PERMIT REQUIRED FOR FUEL PIPING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |
| | AT (561)805-6719 OR E-MAIL [email protected]. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |